4. Operation (LCD model)                                                                                              

                                                    

  4.2.4 LCD indication of UPS alarm status and faults

In the event of an UPS fault, UPS enters fault operation mode, at this point, the fault icon turns on consist

-

ently, the buzzer beeps continuously and the data information area shows current fault code (refer to table 

7-2), the display on the front panel is shown as the figure 5-5, users can switch to output page by pressing 

function button.

When a warning occurred, the fault icon blinks every second, and users can switch to the alarm display page 

shown as the figure 5-6 to check the warning code. 

4.3 Operating Instructions 

 

 

4.3.1 UPS ON/OFF Operation

Note: The battery is fully charged before delivery. However, storage and transportation will inevitably cause 

some charge loss. Therefore, it is advisable to charge the battery for 10 hours before using it, so as to ensure 

adequate battery capacity.

Figure 5-6 Alam display

A02

Figure 5-5 Fault display

F0 1

Содержание Venus Smart 1K

Страница 1: ...HUPHOTIC CO LTD ENERGY WAVE CO LTD CHUPHOTIC ELECTRONICS CO LTD 949 Moo 9 Sumrong Nue Muang Samutprakarn Samutprakarn 10270 Tel 02 186 3011 Fax 02 186 3018 19 Website www chuphotic com E mail ups chup...

Страница 2: ...g Inspection 4 3 2 Installation Notes 4 3 3 Cable Connection 4 5 4 Operation LCD model 6 10 4 1 Operation Display Panel 6 4 2 Operation Mode 6 8 4 3 Operating Instructions 9 10 5 Maintenance 10 11 5 1...

Страница 3: ...Do not short the positive and negative electrodes of battery Otherwise it may cause electric shock or fire 6 Do not plunge or insert any objects into the air vents and other inlets 7 Do not store or...

Страница 4: ...el Remark 1K With a 1A internal charger and 3 build in batteries of 12V 7AH 2K With a 1A internal charger and 6 or 8 build in batteries of 12V 7AH 3K With a 1A internal charger and 8 build in batterie...

Страница 5: ...battery through the DC DC converter 5 Bypass It is very important in the UPS system In the event of a UPS fault that will not lead to UPS shutdown the load will be automatically transferred to the byp...

Страница 6: ...o wait until the UPS fully dried inside out before proceeding to installation and use Otherwise they may be a risk of electric shock 4 Place the UPS near the utility power source outlet which supplies...

Страница 7: ...t on the rear panel of the UPS to complete the connection procedure Note The length of the external battery cable is 1 6 m If users need a longer one please consult the distributor There is a limit to...

Страница 8: ...ndicators The LED indicators contains Bypass indicator utility power indicator Inverter indicator Battery indicator The definition of each indicator is the same as LED panel refer to table 4 1 Table 4...

Страница 9: ...oads connected to the UPS less than 100 capacity of the UPS 3 If the battery indicator blinks it indicates that no battery is connected to the UPS or battery voltage is too low You should check if bat...

Страница 10: ...er another circularly When the battery is fully charged all the level icons are turned on 1 When operating in bypass mode the UPS beeps every 2 minutes If the Function key is pressedfor more than 2 se...

Страница 11: ...switch to output page by pressing function button When a warning occurred the fault icon blinks every second and users can switch to the alarm display page shown as the figure 5 6 to check the warning...

Страница 12: ...s shown on the front panel and no output is available from the UPS outlets system completely power down 2 Completely power down the UPS from Battery mode Press the OFF button persistently for more tha...

Страница 13: ...rature between 15o C and 25o C 3 If the UPS has not been used for a long period charging is recommended at the intervals 3 months 4 Batteries should not be replaced individually 5 Under normal conditi...

Страница 14: ...tributor or service center The 8 utility power LED blinks in normal mode Maybe reversed polarity L N of site wiring or disconnect with ground or the voltage between neutral wiring to protective ground...

Страница 15: ...or Service center F05 On constantly Beep continuously Internal fault Please contact the distributor or Service center F06 On constantly Beep continuously Internal fault Please contact the distributor...

Страница 16: ...every second Battery voltage low The UPS output will be cut off please switch to the backup power A03 Beep once every second UPS power on abnormal Check the battery of the UPS connected properly A05...

Страница 17: ...Standard Charge current 1A 6 5A 1A 5 5A 1A 5 5A Crest factor 3 1 1 The output frequency synchronizes with the input frequency when the input frequency is in the range of 45Hz 55Hz 2 The output freque...

Страница 18: ...IEC61000 4 4 LEVEL4 Surge IEC61000 4 5 LEVEL4 7 Specifications 7 2 Mechanical Item Normal range Ambient temperature 0 C 45 C Environment humidity 0 90 No condensation Altitude Lower than 1000m no dera...

Страница 19: ...odel Intelligent monitor software CD 1 User Manual 1 Serial communication cable 1 UPS 1 Intelligent monitor software CD 1 Long backup time Model User Manual 1 External Battery Cable 1 Serial communica...

Страница 20: ......

Страница 21: ...Service center please Call 02 1863011 AUTO...

Отзывы: