background image

6

MAINTENANCE

The Chromalox STAR-TG tip over cutout with ground fault

sensor provides a reliable and cost effective method for sensing
ground faults and to shut off the heater in case of tip-over. The pur-
pose of the ground fault control is to monitor for ground faults,
sense potential heater failure symptoms and to protect equipment.

The current-carrying wires are routed through the current

transformer on the control. When ground current reaches the level
set by the trip point adjustment, (.03 amps), the relay trips, illumi-
nates the tripped LED and provides an output signal which de-
energizes the magnetic contactor.

ELECTRIC SHOCK HAZARD. Disconnect all power
to heater before installing or servicing kit(s).

Failure to do so could result in personal injury or
property damage. Kit(s) must be installed by a
qualified person in accordance with the National
Electrical Code, NFPA 70.

If heating element(s) fail to operate:

1.

Open door of enclosure. 

DANGER: Hazard of Electric

Shock. 

2.

If "Tripped" indicator is not on, check for blown fuses or failed
electrical components in the heater’s electrical system includ-
ing the tip over trip mechanism.then this indicates one or more
heating elements are about to fail. 

3.

Check pendulums on the tip over switch mechanisms to be sure
they are not blocked.

4.

If the "Tripped" indicator is on, then this indicates one or more
heating elements are about to fail. Disconnect power and fol-
low the GF Troubleshooting Diagram below.

Tripped Indicator

Light is On

Is this the

initial

installation?

Is this the first

time heater is

used for the

season?

Is the set point of
the GF sensor set
at a value less than
.03 amps?

Did the problem
occur after
working properly
during part of this
heating season?

This condition indicates
at least one element is 
about to fail.

Call Chromalox
Service Dept.
1 800-368-2493

Close cover.

Does the

heater

operate?

Does the heater

operate?

1. Replace all elements.
2. Flip toggle switch back
    and forth, one time to
    reset GF sensor.

Do you want to

reduce future

down time and

maintenance

costs?

1. Turn set point dial
    clockwise to .03 amps.
2. Flip toggle switch mounted ontop
    of enclosure back and forth one 
    time, (this resets the GF sensor).

Unbuss wiring, check insulation resistance
on each element.
1. Each element to have at least 10 Meg
    terminal to sheath.
2. If element does not have at least 10 Meg.
    dry out element by applying half of the 
    rated voltage for one hour.
3. Rebuss elements, re-energize heater, flip
    toggle switch back and forth, one time
    to reset GF sensor.

Does the heater

operate?

Call Chromalox
Service Dept.
1 800-368-2493

Does the

heater

operate?

Close all covers.

Unbuss wiring, check insulation resistance
on each element.
1. Each element to have at least 10 Meg
    terminal to sheath.
2. If element does not have at least 10 Meg.
    dry out element by applying half of the  
    rated voltage for one hour.
3. Rebuss elements, re-energize heater, flip
    toggle switch back and forth, one time
    to reset GF sensor.

START

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

Close all covers.

Close all covers.

TG TROUBLESHOOTING DIAGRAM

Содержание DS-50600

Страница 1: ...ds Tip Over Shut Down with Ground Fault Sensor See Pages 5 and 6 Fig 4 GENERAL To use this instruction sheet from Table 1 select the Installation Instructions by matching the Kit Model to the Heater M...

Страница 2: ...r terminal box Remove cover 4 Remove cover from disconnect switch assy using same method as Step3 5 Remove Chase nipple and gasket from opening end of disconnect switch assy Slide Chase nipple through...

Страница 3: ...ace with 3 8 nuts 5 Remove cover from disconnect switch assy using same method as Step 3 6 Remove Chase nipple and gasket from opening end of disconnect switch assy Slide Chase nipple through hole in...

Страница 4: ...element to have at least 10 Meg terminal to sheath 2 If element does not have at least 10 Meg dry out element by applying half of the rated voltage for one hour 3 Rebuss elements re energize heater fl...

Страница 5: ...n studs and secure in place with 3 8 nuts 5 Remove cover from tip over switch assy using same method as Step 3 6 Remove Chase nipple and gasket from open end of tip over switch assy Slide Chase nipple...

Страница 6: ...hooting Diagram below Tripped Indicator Light is On Is this the initial installation Is this the first time heater is used for the season Is the set point of the GF sensor set at a value less than 03...

Страница 7: ...ANSFORMER WHITE TO TERMINALS INSIDE HEATER JUNCTION BOX POWER LEADS MUST PASS THROUGH CURRENT TRANSFORMER POSITION OF GROUND FAULT MONITOR PRI SIDE TRANSFORMER CONNECTION 208V BLK AND RED 240V BLK AND...

Страница 8: ...472 007 132 304689 001 132 304879 002 056 304884 004 NA NA NA NA NA STAR GF 8 STAR GF 3 STAR GF 4 072 121651 062 STAR GF 7 STAR GF 6 STAR TIP 8 STAR TIP 2 STAR TIP 3 NA NA NA NA 303 052241 002 303 052...

Отзывы: