background image

(Supersedes PG436-1)

PG436-2

VTS

161-304901-004

JUNE, 2010

4

DATE

SALES

REFERENCE

DIVISION

SECTION

Chromalox

®

DS-50600, STAR-GF, STAR-TIP and STAR-TG Kits

For Adding Optional Kits to STAR Radiant Heaters

© 2008 Chromalox, Inc.

Table 1

Kit Model

Used with Heater Model

Kit Function

Installation Instructions

Wiring Diagram

DS-50600

Fixed STAR-06A and STAR-14A

Adds Integral Disconnect Switch

See Page 2

Fig. 1

DS-50600

Portable STAR-06A and STAR-14A

Adds Integral Disconnect Switch

See Page 3

Fig. 1

STAR-GF

All Fixed STAR

Adds Wall Mounted Ground Fault Sensor

See Page 4

Fig. 2

STAR-TIP

Portable STAR-06A and STAR-14A

Adds Tip Over Shut Down

See Page 5

Fig. 3

STAR-TG

Portable STAR-06A and STAR-14A

Adds Tip Over Shut Down with Ground Fault Sensor

See Pages 5 and 6

Fig. 4

GENERAL

To use this instruction sheet from Table 1 select the Installation

Instructions by matching the Kit Model to the Heater Model. If a
match does not exist consult Factory.

The kits are add-on options to STAR Radiant Heaters. The

installation and renewal parts identification for the heater is cov-
ered in the instruction sheet provided with the heater. 

SAVE

BOTH COPIES OF THE INSTRUCTION SHEET.

ELECTRIC SHOCK HAZARD. Disconnect all power
to heater before installing or servicing kit(s).
Failure to do so could result in personal injury or
property damage. Kit(s) must be installed by a
qualified person in accordance with the National
Electrical Code, NFPA 70.

Always check to make certain the voltage rating of the kit

matches the voltage rating of the heater (See Nameplates).

Model DS50600

STAR-GF

Model STAR-TIP 

STAR-TG

Содержание DS-50600

Страница 1: ...ds Tip Over Shut Down with Ground Fault Sensor See Pages 5 and 6 Fig 4 GENERAL To use this instruction sheet from Table 1 select the Installation Instructions by matching the Kit Model to the Heater M...

Страница 2: ...r terminal box Remove cover 4 Remove cover from disconnect switch assy using same method as Step3 5 Remove Chase nipple and gasket from opening end of disconnect switch assy Slide Chase nipple through...

Страница 3: ...ace with 3 8 nuts 5 Remove cover from disconnect switch assy using same method as Step 3 6 Remove Chase nipple and gasket from opening end of disconnect switch assy Slide Chase nipple through hole in...

Страница 4: ...element to have at least 10 Meg terminal to sheath 2 If element does not have at least 10 Meg dry out element by applying half of the rated voltage for one hour 3 Rebuss elements re energize heater fl...

Страница 5: ...n studs and secure in place with 3 8 nuts 5 Remove cover from tip over switch assy using same method as Step 3 6 Remove Chase nipple and gasket from open end of tip over switch assy Slide Chase nipple...

Страница 6: ...hooting Diagram below Tripped Indicator Light is On Is this the initial installation Is this the first time heater is used for the season Is the set point of the GF sensor set at a value less than 03...

Страница 7: ...ANSFORMER WHITE TO TERMINALS INSIDE HEATER JUNCTION BOX POWER LEADS MUST PASS THROUGH CURRENT TRANSFORMER POSITION OF GROUND FAULT MONITOR PRI SIDE TRANSFORMER CONNECTION 208V BLK AND RED 240V BLK AND...

Страница 8: ...472 007 132 304689 001 132 304879 002 056 304884 004 NA NA NA NA NA STAR GF 8 STAR GF 3 STAR GF 4 072 121651 062 STAR GF 7 STAR GF 6 STAR TIP 8 STAR TIP 2 STAR TIP 3 NA NA NA NA 303 052241 002 303 052...

Отзывы: