WIRING

For applicable wiring diagram see Table 1

GROUND FAULT
MONITOR

TOGGLE SWITCH

SEE NOTES

ATTACHED TO
AUXILLARY TERMINALS

NOTES:
1. USE 90 DEG. C. MIN. WIRING.
2. USE COPPER CONDUCTORS ONLY.
3. VERIFY THAT VOLTAGE OF "STAR-TG"
    MATCHES VOLTAGE OF HEATER.

BLACK

TRANSFORMER

WHITE

TO TERMINALS
INSIDE HEATER
JUNCTION BOX

POWER LEADS MUST
PASS THROUGH CURRENT
TRANSFORMER POSITION
OF GROUND FAULT 
MONITOR

PRI. SIDE TRANSFORMER CONNECTION:
208V = BLK AND RED
240V = BLK AND ORG
277V = BLK AND BRN
380V = BLK AND VIOLET
480V = BLK AND BLK/RED
600V = BLK AND GRAY
UNUSED LEADS CAPPED OFF.

SUPPLY

CONTACTOR

CO

NC

NO

L2

L3

L1

1

3

2

G

L3
L2

GROUND FAULT
MONITOR

TOGGLE

SWITCH

TIPOVER

SWITCH

TIPOVER

SWITCH

CONTACTOR

SEE NOTES

ATTACHED TO
AUXILLARY
TERMINALS

NOTES:
1. USE 90 DEG. C. MIN. WIRING.
2. USE COPPER CONDUCTORS ONLY.
3. VERIFY THAT VOLTAGE OF "STAR-TG"
    MATCHES VOLTAGE OF HEATER.

BLACK

TRANSFORMER

WHITE

TO TERMINALS
INSIDE HEATER
JUNCTION BOX

POWER LEADS MUST
PASS THROUGH CURRENT
TRANSFORMER POSITION
OF GROUND FAULT 
MONITOR

PRI. SIDE TRANSFORMER CONNECTION:
208V = BLK AND RED
240V = BLK AND ORG
277V = BLK AND BRN
480V = BLK AND BLK/RED
380V = BLK AND VIOLET
600V = BLK AND GRAY
UNUSED LEADS CAPPED OFF.

SUPPLY

CO

NC

NO

3

2

1

L1

TOGGLE
SWITCH

TIPOVER
SWITCH

TIPOVER
SWITCH

CONTACTOR

TRANSFORMER

BLACK

WHITE

TO TERMINALS
INSIDE HEATER
JUNCTION BOX

NOTES:
1. USE 90 DEG. C. MIN. WIRING.
2. USE COPPER CONDUCTORS ONLY.
3. VERIFY THAT VOLTAGE OF "STAR-TIP"
    MATCHES VOLTAGE OF HEATER.

PRI. SIDE TRANSFORMER CONNECTION:
208V = BLK AND RED
240V = BLK AND ORG
277V = BLK AND BRN
380V = BLK AND VIOLET
480V = BLK AND BLK/RED
600V = BLK AND GRAY
UNUSED LEADS CAPPED OFF.

3

L3
L2
L1

2
1

1

2

4

3

6

5

DISCONNECT

SWITCH

TERMINAL BLOCK

NOTES:
1. USE 90 DEG. C. MIN. WIRING.
2. USE COPPER CONDUCTORS ONLY.
3. TO MAINTAIN THE ENVIRONMENTAL
    RATING OF THIS ENCLOSURE, USE
    ONLY UL LISTED OR RECOGNIZED
    LIQUID TIGHT CONDUIT HUBS.

TO TERMINALS
INSIDE HEATER
JUNCTION BOX

3

2

1

GRN L1

L2

L3

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Содержание DS-50600

Страница 1: ...ds Tip Over Shut Down with Ground Fault Sensor See Pages 5 and 6 Fig 4 GENERAL To use this instruction sheet from Table 1 select the Installation Instructions by matching the Kit Model to the Heater M...

Страница 2: ...r terminal box Remove cover 4 Remove cover from disconnect switch assy using same method as Step3 5 Remove Chase nipple and gasket from opening end of disconnect switch assy Slide Chase nipple through...

Страница 3: ...ace with 3 8 nuts 5 Remove cover from disconnect switch assy using same method as Step 3 6 Remove Chase nipple and gasket from opening end of disconnect switch assy Slide Chase nipple through hole in...

Страница 4: ...element to have at least 10 Meg terminal to sheath 2 If element does not have at least 10 Meg dry out element by applying half of the rated voltage for one hour 3 Rebuss elements re energize heater fl...

Страница 5: ...n studs and secure in place with 3 8 nuts 5 Remove cover from tip over switch assy using same method as Step 3 6 Remove Chase nipple and gasket from open end of tip over switch assy Slide Chase nipple...

Страница 6: ...hooting Diagram below Tripped Indicator Light is On Is this the initial installation Is this the first time heater is used for the season Is the set point of the GF sensor set at a value less than 03...

Страница 7: ...ANSFORMER WHITE TO TERMINALS INSIDE HEATER JUNCTION BOX POWER LEADS MUST PASS THROUGH CURRENT TRANSFORMER POSITION OF GROUND FAULT MONITOR PRI SIDE TRANSFORMER CONNECTION 208V BLK AND RED 240V BLK AND...

Страница 8: ...472 007 132 304689 001 132 304879 002 056 304884 004 NA NA NA NA NA STAR GF 8 STAR GF 3 STAR GF 4 072 121651 062 STAR GF 7 STAR GF 6 STAR TIP 8 STAR TIP 2 STAR TIP 3 NA NA NA NA 303 052241 002 303 052...

Отзывы: