Installation
3-19
Command
Parameter
Description
SOURce:POW?
None
Float. Query power setting value.
Syntax: SOURce:POW?
Parameter: None
Return Value: 50.025
Command
Parameter
Description
SOURce:VOLTage:CUTOFF Voltage
Cutoff Value
Float. Set the cutoff voltage parameters. Unit
(V). There are three decimal points. Range
based on machine specifications.
Syntax: SOURce:VOLTage:CUTOFF
Parameter: 20.000
Return Value: None
Command
Parameter
Description
SOURce:VOLTage:CUTOFF? None
Float. Query cutoff voltage setting value.
Syntax: SOURce:VOLTage:CUTOFF?
Parameter: None
Return Value: 20.000
Command
Parameter
Description
SOURce:CURRent:CUTOFF Current
Cutoff Value
Float. Set the cutoff current parameters. Unit
(A). There are three decimal points. Range
based on machine specifications.
Syntax: SOURce:CURRent:CUTOFF
Parameter: 3.000
Return Value: None
Command
Parameter
Description
SOURce:CURRent:CUTOFF? None
Float. Query cutoff current setting value.
Syntax: SOURce:CURRent:CUTOFF?
Parameter: None
Return Value: 3.000
Command
Parameter
Description
SOURce:SLEW
Current Slew Rate
Float. Set the current slew rate parameters. Unit
(A). There are three decimal points. Range
based on machine specifications.
Syntax: SOURce:SLEW
Parameter: 0.100
Return Value: None
Command
Parameter
Description
SOURce:SLEW?
None
Float. Query current slew rate setting value.
Syntax: SOURce:SLEW?
Parameter: None
Return Value: 0.100
Command
Parameter
Description
SOURce:MODe
Operation Status String. Set the operation status parameters.
CCC: CC Charge
Содержание 69200-1
Страница 1: ......
Страница 2: ......
Страница 3: ...Charge Discharge Controller 69200 1 User s Manual Version 1 3 April 2017...
Страница 8: ...vi...
Страница 12: ......
Страница 14: ......
Страница 20: ......
Страница 70: ......
Страница 78: ......
Страница 80: ...Charge Discharge Controller 69200 1 User s Manual 5 2 please notify Chroma for calibration...
Страница 82: ......
Страница 84: ......