7
E461755
Max. Current [A]
Min. Current [A]
0,000 - 16,00 A
0,000 - 16,00 A
Maximum current of the
measuring.
Minimum current of the
measuring.
Max. real power
[W]
Min. real power
[W]
0,0 - 4224 W
0,0 - 4224 W
Maximum real power of
the measuring.
Minimum real power of
the measuring.
ON Time [%]
ON Time [h]
0,00 - 100,0 %
00:00 - 9999:59 h
Percent and time over
the adjusted ON-
threshold.
(Standby-threshold)
2.3.3.
Description of the ON%-function
Many consumers (e.g. refrigerator) not constantly need the full
achievement from the net. Therefore it is good to be known which time a
consumer really needs the full electrical power and not only works in the
standby-mode.
The function indicates how much percent of the measured time and how
many hours the consumers worked over the adjusted ON-threshold
(Standby-threshold).
The following diagram illustrates the measurement principle.
Display
Mode of operation Range
Meaning
„ON%“-Time
t
Start
Stop
Start
t
Real power
ON-
threshold
(Standby-
thereshold
S
ta
n
d
-b
y
S
ta
n
d
-b
y
RESET
7(9)
Amax
0.231
0.196
Amin
RESET
8(9)
Wmax
43.7
34.9
Wmin
RESET
9(9)
ON%
82,5
10:02
ONh