Appendix A: Features and Specifications
24
ACTIVE Series UPS User Instruction Manual
Specifications
UPS Model
A07KXAU
A1K0XAU
A1K5XAU
A2K0XAU
A3K0XAU
A2K0XHU
A3K0XHU
Part number
A07KXAU
A1K0XAU
A1K5XAU
A2K0XAU
A3K0XAU
A2K0XHU
A3K0XHU
Maximum load (VA/W)
700 VA/490 W
1000 VA/700 W 1500 VA/1050 W 2000VA/1400 W 3000 VA/2100 W 2000 VA/1400 W
3000 VA/2100 W
Acceptable input voltage range (VAC)
80-142
160-280
Nominal input voltages (VAC)
120 (factory default) 100, 127 (selectable)
208 (factory default)
200, 208, 220, 230, 240 (selectable)
Input frequency
50/60 Hz ±5, auto-select, input frequency 40-70 Hz
Nominal output voltages (V)
120 (factory default) 100, 127 (selectable)
208 (factory default)
200, 208, 220, 230, 240 (selectable)
Output current @ 120 V (A)
@ 208 V (A)
5.8
NA
8.3
NA
12.5
NA
16.7
NA
25
NA
NA
9.6
NA
14
Output frequency
50/60 Hz ±0.5%, frequency converter (selectable)
Frequency tolorance, normal operation
output frequency is synchronized with the maximum frequency
Output waveform
Sinusoidal
Overload capacity
< 110% warning
110% - 130%: 12 seconds, switches to bypass
>130% - 1.5 seconds, switches to bypass
contact technical service for further details
Input connection
5-15P
L5-20P
L5-30P
IEC320 to L6-20P IEC320 to L6-30P
Output connection
(8) 5-15R
(4) 5-20R & (1)
L5-20R
(4) 5-20R & (1)
L5-30R
IEC (contact factory for IEC to
NEMA adapters)
Port standard
(1) serial, (1) USB
Comm slot
1 slot for SNMP/Web Interface
Internal battery
(3) 12 V YUASA NP7-12FR
(3) 12 V YUASA
REW45-12FR
(6) 12 V YUASA
NP7-12FR
(6) 12 V YUASA
REW45-12FR
(6) 12 V YUASA
NP7-12FR
(6) 12 V YUASA
REW45-12FR
Battery type
sealed, maintenance-free lead acid, VRLA
Battery test
Automatic, once per month (adjustable through UPS management software supplied)
Battery management
EXB auto recognition, automatic runtime adjustment, protection against deep discharge
UPS dimensions - HxWxD - in. (cm)
3.4 x 17.2 x 19.2 (8.64 x 43.7 x 48.7)
3.4 x 17.2 x 26.3 (8.64 x 43.7 x 66.8)
UPS ship weight - lbs(kg)
56 (25)
60 (27)
60 (27)
85(39)
86 (39)
85 (39)
86 (39)
External battery (maximum 4 per UPS)
A
BP1K5-2; (6)
12 V YUASA NP7-12FR
A
BP3K0-2; (6)
12 V YUASA REW45-12FR
External Battery Dimensions - HxWxD - in. (cm)
3.4 x 17.2 x 19.2 (8.64 x 43.7 x 48.7)
3.4 x 17.2 x 26.3 (8.64 x 43.7 x 66.8)
External battery ship weight - lbs (kg)
64 (29)
107 (49)
Interfaces COM A
9 pin SUB-D pin contacts
Operating temperature
32°F to 104°F (0°C to 40°C)
recommended 50°F to 77°F (10°C to 25°C)
Storage temperature
5°F to 120°F (-15°C to 50°C)
recommended 50°F to 77°F (10°C to 25°C)
Relative humidity
20% to 90%, non-condensing
Heat dissipation (max.) (BTU/hr)
275
390
584
1004
1158
810
1158
EMC
FCC part 15, class B, EN 61000-6-1,
EN 61000-602, EN 55024
FCC part 15, class A, EN 61000-6-1, EN 61000-602, EN 55024
Содержание ACTIVE A0K7XAU
Страница 3: ......
Страница 5: ...ii ACTIVE User Instruction Manual ...