UPS Start-up & Shutdown
ACTIVE Series UPS User Instruction Manual
15
Fig. 13: Rear Panel External Battery Pack
1. Battery Power Receptacle (input from UPS) 3. Battery Power Receptacle (output to additional battery)
2. Battery Circuit Breaker
4. Battery Counter Connector
UPS Start-up &
Shutdown
ATTENTION:
This UPS is supplied with standard power cords and receptacles suitable for its use in
your area of operation. It may be installed and operated by non-tchnical personnel.
ATTENTION:
When the UPS is started for the first time, AC Power must be present.
When using the UPS for the first time, confirm AC power is present and press
.
The UPS will respond first with a brief beep followed by a brief illumination of all LED indicators. The
UPS will then sound two brief beeps, and turn on the ON-LINE LED indicating that the unit is now in
ON-LINE mode.
Power should now be available to the connected equipment.
Normal UPS Start-up
Procedure
Press the
button.
The UPS will respond first with a brief beep followed by a brief illumination of all LED indicators.
If AC power is present, the UPS will sound two brief beeps, and turn on the ON-LINE LED indicating
that the unit is now in ON-LINE mode.
If AC power is not present, the UPS will sound five brief beeps and turn on the ON-BATTERY LED
indicating that the unit is now providing output power from the battery.
ATTENTION: If the overload indicator is on, or the “LOAD” indicator is beyond 100%, there are too
many devices connected to the UPS. If only one device is connected to the UPS and the overload indicator
is on, then the load’s power demand exceeds the rating of the UPS, and a UPS with a higher power rating
must be used
NOTE: If the UPS does not respond as above, please see “Troubleshooting” on page 21.
Manual Bypass
Procedure
To place the UPS into bypass mode, press and hold buttons 9 and 10 for 5 seconds (see figure 9 on page
11). The UPS will switch to bypass mode and the BYPASS LED will illuminate.
UPS Shutdown
Procedure
Press the
button. The UPS will turn off all outputs, and shutdown.
To restart UPS see “Normal UPS Start-up Procedure” on page 15.
WARNING: This equipment receives power from more than one source. The output receptacles may have
voltage even when the unit is turned off.
Remote Power Off
(RPO)
The external connection to the RPO circuit is located next to the 9-pin SUB-D (interface RS232)
connector in the upper rear of the unit. If the circuit between the two RPO connector pins is “opened,” the
output of the UPS is immediately switched off. To restart the UPS, the procedures outlined in the “UPS
Start-up Procedure” must be followed. The RPO circuit may be extended by connecting the “normally
closed” switches in series between the RPO connector pins. Activating (opening) any of the series
switches will cause the UPS to shut off its output.