Maintenance
ACTIVE Series UPS User Instruction Manual
17
The manufacturer’s service center is fully equipped to deal with such batteries, in accordance with the law and
with the greatest respect for the environment. Contact Technical Support to arrange for maintenance and/or
battery replacement.
The typical battery life cycle is 3 to 5 years, at an ambient temperature of 77°F (25°C), however battery life is
also dependent on the frequency and duration of mains failures or battery discharge cycles.
The BATTERY TEST (see section titled “Battery Test”) should be carried out periodically (6 to 12 months) in
order to ascertain the general condition of the batteries.
To replace internal batteries:
1. Place the UPS manually in bypass mode, see “Manual Bypass Procedure” on page 15.
2. On the left side of the front cover, locate the indentation.
3. Place fingers of left hand into the indentation, and pull forward until the left side of the front cover “snaps”
out of position.
4. Remove the left side of the front cover and place it in a safe place.
5a.
On 700 VA, 1000 VA, and 1500 VA:
Remove one screw on the right side of the battery retention plate that
is now exposed on the front left side of the UPS.
Disconnect battery connectors.
Fig. 14: Removing Front Cover and Battery Retention Plate
5b.
On 2000 VA and 3000 VA:
Disconnect battery connectors.
Remove one screw on the right side of the battery retention plate that is now exposed on the front left side
of the UPS.
ATTENTION: Battery pack is heavy. Use two hands when removing pack from unit
6. Slide out battery pack.
Fig. 15: Removing Battery
7. Slide in replacement battery pack.
8a.
On 700 VA, 1000 VA, and 1500 VA:
Re-connect the battery connectors.
Replace metal battery retention plate with screw.
8b.
On 2000 VA and 3000 VA:
Replace the metal battery retention plate with screw.
Re-connect battery connectors.
9. Align left plastic front.
10. Snap battery front cover into place.
11. Carefully pack used battery pack and send to authorized recycle center.
Battery
Battery Retention Plate
Front Cover
Screw