- 1 x RS232 interface cable
- 1 x USB cable
- 2 x front brackets for rack-mounting and required mounting hardware
- 2 x sets of tower feet for
fl
oor-mounting
- 2 x sliding rail kits for rack-mounting (optionally) and required mounting hardware
3.3.4 Rack/Tower units (battery packs)
- 1 x Battery Pack unit
- 1 x battery extension cable
- 1 x battery pack detection cable for auto-detection of number of battery packs connected
- 2 x front brackets for rack-mounting and required mounting hardware
- 2 x spacers to be assembled with the sets of tower feet for
fl
oor-mounting
- 1 x plate for securing the battery pack to the UPS for
fl
oor-mounting
- 2 x sliding rail kits for rack-mounting (optionally) and required mounting hardware
3.4 Storage
If it is not intended that the UPS be used within seven days of delivery, attention shall be paid to the storage
conditions.
The UPS should be stored in a clean, dry environment and away from temperature extremes. It is
recommended that the unit be stored in a temperature controlled, moderate humidity environment. The
table below provides the temperature and humidity storage limits:
3.5 Handling
The UPS must be kept upright at all times and handled with care. Damage may be caused if dropped or
subjected to severe impact.
3.6 Environmental Conditions
The UPS tower version must be installed vertically. The UPS rack/tower version (RT hereinafter) can be
installed vertically or horizontally, depending on the desired arrangement.
In any case, it must be installed on a level and even surface and in an area protected from extremes of
temperature, water, humidity and the presence of conductive powder or dust (see section 3.10). Do not
stack units and do not place any objects on top of a unit.
The functional temperature range of the UPS is speci
fi
ed in section 8 (“Technical Speci
fi
cations”).
The ideal ambient temperature range is 15ºC to 25ºC.
Expected battery runtimes and battery life is de
fi
ned at 20ºC. Increments of temperature above 25ºC will
reduce the expected battery life.
1000, 1500 and 2000VA models
3000VA models
2 x connection cables IEC320
C14 (male) - IEC C13 (female)
for the UPS output
1 x connection cable Schuko
(male) - IEC320 C19 (female) for
the UPS input
1 x multisocket extension
IEC320 C20 (male) - 3 x Schuko
(female) for the UPS output
Temperature limits
-25ºC/50ºC (w/o batteries)
-15ºC/40ºC (with batteries)
Relative humidity (non-
condensing)
10-90%
Содержание 2000
Страница 1: ...UK ...
Страница 2: ...1 Chloride Active UK ...
Страница 3: ...1 Chloride Active ENGLISH DEUTSCH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS UK DE E FR I P ...
Страница 38: ...36 UK Chloride Active 945044 066 Tower models Rack Tower models ...
Страница 76: ...74 DE Chloride Active 945044 066 Tower Modelle Rack Tower Modelle ...
Страница 114: ...112 E Chloride Active 945044 066 Equipos torre Equipos rack torre ...
Страница 152: ...150 FR Chloride Active 945044 066 Matériels colonnes Matériels rack colonnes ...
Страница 190: ...188 I Chloride Active 945044 066 Apparecchi tower Apparecchi rack tower ...
Страница 228: ...226 P Chloride Active 945044 066 Equipamentos torre Equipamentos rack torre ...
Страница 234: ...235 Chloride Active P www chloridepower com 945044 066 Ed 2 Feb 08 ...