2.2 Wiring and Connections
This section contains wiring diagrams for the various connections that are possible for this Gateway.
The Gateway has 3 main ports:
Port 0
This port is a RS485 port and is used primarily for Modbus RTU. It can support full and half duplex
RS485.
Port 1
This port is setup a RS232 port and is
NOT
used by the Gateway.
Ethernet Port
This port is used by the TCP/IP and UDP drivers of the Gateway. Default port for accessing the internal
web server of the Gateway is 80.
3. Setting up the Gateway
This section contains information and instructions on what to do when connecting to the Gateway for
the first time.
3.1 Determining the IP Address
Before connecting to the Gateway, you will need to determine the IP Address of the Gateway. By
default, the Gateway is assigned a Static IP Address of
192.168.1.113
when it is shipped.
To find the IP Address, look on the back of the Gateway. There should be a business card attached to
the back of the Gateway that has the IP Address and Reference #. See below for an example
Image 3.1 – Business Card attached to back of CAS Gateway
Take note of the Ref# as this will be used by the support team to pull up additional information about
the project.