106
Po/Pn(%)
100%
80%
60%
40%
20%
0
0.88Un 1.0Un 1.1Un
Figure 8-3
CPS SCH100/125KTL-US-600 and SCH100KTL-US-480 Derating Curve of
Grid Voltage
When the grid Voltage is within 100%
~110% of the rated output voltage, the
inverter output power may reach 100%. When the grid voltage is lower than
100%, the inverter will limit the AC Output Current and the output power will
begin to derate, as shown in Figure 8-3.
Содержание CPS SCH Series
Страница 2: ......
Страница 4: ......
Страница 43: ...39 Figure 3 25 AC Output Cable Connection Distributed Wire box L1 L2 L3 ...
Страница 45: ...41 Figure 3 27 AC Output Cable Connection Centralized Wire box Ver 2 ...
Страница 58: ...54 Figure 4 1 System setting ...
Страница 60: ...56 Figure 4 2 Normal Operation Status Summary Screen SWIPE TO CHANGE MENUS SEE MENUS IN SECTION 5 4 ...
Страница 81: ...77 5 4 2 6 Others The REF column is reference to Table 5 7 Enable functions ...