68
5.4.2.2 Active Power Derating
The
Active Power Derating
menu is used to set the active
power derating parameters including Active Power Derating, Over
frequency derating and High temperature frequency derating, etc.
The parameters are shown in Table 5-2. To make permanent
changes to these settings either on-site or via the Flex Gateway
Portal, the Active Power Mode in Table 5.7 (3) must be set to ”Local
Control”. The setting made in the “Remote Dispatch Mode” will reset
when DC Power Cycles.
Grid voltage
100.00%~135.00%
Settable
Power
Present
0
0.0%~100.0%
Settable
GridV.Max1
Figure 5-3 Curve of over voltage derating
Grid Frequency
60.00~72.00Hz
Settable
Power
Present
0
0.0%~100.0%
Settable
GridF.Max1
Figure 5-4 Curve of over frequency derating