7
2.3 Product Protection Functions
✓
Reverse polarity protection of DC input
✓
AC and DC Short circuit protection
✓
Anti-islanding protection with bi-directional frequency perturbation
✓
DC Input and AC output over-voltage protection
✓
DC Input over-current protection
✓
DC input insulation against ground monitoring
✓
DC injection of AC output
✓
AC output voltage and frequency monitoring
✓
Leakage current against ground monitoring
✓
External environmental temperature monitoring
✓
IGBT power module temperature monitoring
2.4 Smart Inverter Functions and default Activation
Function
IEEE1547-2014 Rule 21
ISO-NE
Anti-islanding
Enabled
Enabled
Enabled
Low/High Voltage Ride-Though N/A
Enabled
Disabled
Low/High Frequency Ride-
Though
N/A
Enabled
Enabled
Dynamic Volt/VAR Operation
N/A
Enabled
Disabled
Ramp Rate
N/A
Enabled
Enabled
Fixed Power Factor
N/A
Disabled
Disabled
Reconnect by “Soft-Start”
N/A
Enabled
Enabled
Frequency-Watt
N/A
Enabled
Disabled
Volt/Watt
N/A
Enabled
Disabled
Содержание CPS SCH Series
Страница 2: ......
Страница 4: ......
Страница 43: ...39 Figure 3 25 AC Output Cable Connection Distributed Wire box L1 L2 L3 ...
Страница 45: ...41 Figure 3 27 AC Output Cable Connection Centralized Wire box Ver 2 ...
Страница 58: ...54 Figure 4 1 System setting ...
Страница 60: ...56 Figure 4 2 Normal Operation Status Summary Screen SWIPE TO CHANGE MENUS SEE MENUS IN SECTION 5 4 ...
Страница 81: ...77 5 4 2 6 Others The REF column is reference to Table 5 7 Enable functions ...