33
3.
Parameters
Fan coil parameter list for MD1001 controller (V2.0)
No.
Meaning
Range
Default
Level
01
Target temp upper limit, Maximum Temperature, user setting
60°F ~ 205°F
86°F
Factory
02
Target temp lower limit, Minimum Temperature, user setting
60°F ~ 205°F
46°F
Factory
03
Target temp in cooling mode. If the room temp is ≥ 79°F, the
fan will come on. If the room temp is ≤ 78°F, the fan will turn
off.
78°F
End user
04
Target temp in heating mode. If the room temp is ≤ 67°F, the
fan will come on. If the room temp is ≥ 68°F, the fan will turn
off.
68°F
End user
05
Automatic mode target cooling temp. If the room temp is
≥ 79°F the fan will come on in cooling mode. If the room temp
is ≤ 78°F and parameter 20=1,the fan coil will run for 1 min.
every 15 min.
78°F
Factory
06
Automatic mode target heating temp. . If the room temp is
≤67°F the fan will come on in Heating mode. If the room temp
is 68°F and parameter 20=1,the fan coil will run for 1 min.
every 15 min.
68°F
Factory
07
In heating mode, if the coil temp is lower than Parameter 07,
the fan motor will stop. See CX30 heating set temperature.
41°F ~ 104°F
77°F
Factory
08
In cooling mode, if the coil temp. is higher than 68°F, the fan
motor will stop. (1-Yes; 0-No)
0 ~ 1
1
Factory
09
Start the ultra-low fan speed (1-Yes; 0-No)
0 ~ 1
0
Factory
10
Is there a water valve (1-Yes; 0-No)
0 ~ 1
1
Factory
11
Is there floor heating (1-Yes; 0-No)
0 ~ 1
0
Factory
12
Display in Fahrenheit (1-°F; 0-°C)
0 ~ 1
1
Factory
13
Is it the main controller (1-Yes; 0-No)
0 ~ 1
0
Factory
14
Address
1 ~ 99
15
Factory
15
Lock the button (1-Yes; 0-No)
0 ~ 1
0
Factory
16
When the button is locked, is the remote controller working?
(1-Yes; 0-No)
0 ~ 1
1
Factory
17
Is there a password that should be input before locking the
button? (1-Yes; 0-No)
0 ~ 1
0
Factory
18
Password 1
0 ~ 99
50
Factory
19
Password 2
0 ~ 99
50
Factory
20
In standby mode, the fan motor will intermittently turn on
and off. (1-Yes; 0-No)
0 ~ 1
1
Factory
Содержание CXI120
Страница 17: ...17 Please note The chart above refers to GPM per Fan Coil and not GPM per CX30...
Страница 31: ...31...
Страница 40: ...40 9 Exploded Views Chiltrix CXI34...
Страница 42: ...42 Chiltrix CXI65...
Страница 44: ...44 Chiltrix CXI85...
Страница 46: ...46 Chiltrix CXI120...
Страница 48: ...48 Chiltrix CXI148...
Страница 50: ...50...