Alarm values are entered in pairs with the first value being the min alarm threshold and the
second being the max threshold. If the min threshold is set to %00, then the min alarm is
disabled since no sensor value can be less then 0. If the max threshold is set to %FF, then
the max alarm is disabled since no sensor value can be greater then 255. In this way, various
min and max alarms can be disabled.
In this example row 2 contains the hexadecimal value %20 which translates to 32 decimal.
This value is associated with the 32ed row of the OIL pressure lookup table and indicates
the min OIL pressure alarm will sound if the scaled sensor value drops below 32ed row. If
the 32ed row in the OIL Pressure calibration table corresponds to the display value of 10
PSI then the alarm will sound when pressure drops below 10 PSI. Since the max alarm (row
3) is set to %FF (255 decimal) the max alarm is disabled. In other words, the values used in
the Alarm Table are row indexes in the matching Calibration tables used to trigger alarm
events.