background image

Page 6 

Section 4 - 

 

Front Panel Operation 

 

4.1

 

Introduction 

The  front  panel  consists  of  a  128x32  pixel  monochrome  graphic  OLED  display  with  6 

membrane  key  switches  below  it.  Each  switch  has  legends  on  and  above  or  below  it  to 
indicate  its  function  under  different  conditions,  although  there  are  certain  common 
functions to each screen, as detailed below.  
 
For the purpose of the following sub-sections, the switches shall be referred to using the 
legends on the buttons. 
 

4.2

 

Common Switch Functions 

The switches on certain types of screens and in certain modes, have the same functionality 
as detailed here: 
 

(a)

 

Menu screens 

On the menu screen, the ‘

’ & ‘

’ switches are used to navigate through the menu 

options. The ‘

Func

’ switch is used to go back to the main screen. The ‘

Zero

’ switch 

doubles  up  as  an  Enter  switch  and  this  actions  the  chosen  menu  selection.  This 
may  be  to  go  to  a  sub-menu  or  to  an  editable  or  information  screen  (see  HMI 

breakdown for more details).  

(b)

 

Editable screens 

On  any  screen  that  has  editable  fields,  switches  ‘

’  &  ‘

’  move  the  selection 

between the possible editable fields. ‘

Func

’ goes back to the parent screen which is 

usually the menu that was used to get to the screen in question. ‘

Zero

’ activates edit 

mode (see below). 

(c)

 

Edit mode 

When in edit mode, the edit cursor appears on the first character in the editable field 

(the cursor is a horizontal bar below the character being edited). If the field is bigger 
than 1 character then switches ‘

’ & ‘

’ are used to move left and right across the 

field.  If  the  field  is  only  one  character  (e.g.  a  Yes/No  selection)  or  has  a  rolling 
selection  (e.g.  for  selection  of  a  percentage)  then  ‘

’  &  ‘

’  do  nothing.  Switches 

’ & ‘

’ are used to change the character being edited within the valid range (field 

position dependant). ‘

Func

’ cancels edit mode and returns the field to it’s previous 

value. ‘

Zero

’ accepts any changes to the field and also comes out of edit mode. 

Содержание CCD100

Страница 1: ...e House Folgate Road North Walsham Norfolk NR28 0AJ ENGLAND Tel 01692 500555 Fax 01692 500088 Chell Configurable Display CCD100 OPERATING MANUAL e mail info chell co uk Visit the Chell website at http...

Страница 2: ...in this manual may impair the user s protection Chell Document No 900219 Issue 1 0 ECO Date 20th February 2018 Chell s policy of continuously updating and improving products means that this manual may...

Страница 3: ...Main Screen changing Setpoint 7 c Main Screen Setpoint Valve Control 8 d Main Menu Screen 9 e Setpoint Screen Excitation Screen if millivolt option fitted 9 f Input Screen 10 g Comms Screen 11 h Filte...

Страница 4: ...lc 23 c Retrieve all settings ras 23 SECTION 7 PRINCIPLES 24 7 1 INTRODUCTION 24 7 2 ANALOGUE INPUTS 24 a Range 24 b Full Scale Voltage 24 c Units String 24 7 3 ANALOGUE OUTPUTS 24 7 4 SETPOINT CONTRO...

Страница 5: ...display the output from a pressure transducer It supports both voltage transducers typically 5 10V full scale and also millivolt transducers max 250mV full scale There is also a secondary channel whic...

Страница 6: ...accuracy 15 minutes assumes unit already stabilised at ambient and excludes transducer warm up time 2 3 Measurement and Outputs Power supply out 15V dc 250mA max 24V dc 300mA max Use 15V or 24V trans...

Страница 7: ...V Supply 15 Earth Chassis All other pins Not Connected If the transducer is being powered from another source e g a mains powered supply it will only be necessary to connect to the two signal pins Not...

Страница 8: ...positive conductor to the centre pin Connect the negative 0V conductor to the outer of the jack If requested a compatible AC DC switch mode power supply will have been supplied with the unit Cautions...

Страница 9: ...lection This may be to go to a sub menu or to an editable or information screen see HMI breakdown for more details b Editable screens On any screen that has editable fields switches move the selection...

Страница 10: ...t mode override active for 2 seconds override mode Change setpoint mode to AUTO Change setpoint value main screen changes as below override mode Change setpoint mode to OPEN Change setpoint value main...

Страница 11: ...a specific value the setpoint mode can be changed to Open or Closed which overrides any previously set value Again the main screen shows everything as normal but with the addition of the OPEN or CLOSE...

Страница 12: ...for selection of any menu item Special note for millivolt option If the millivolt option is fitted then the Setpoint menu option will be listed as Excitation to allow for configuration of the initial...

Страница 13: ...assign a units label up to 5 characters for the channel data The number of decimal places selected on the range field dictates the number of decimal places shown for the input channel data on the Main...

Страница 14: ...and buffer size of the adaptive filter The filter only applies to the display and comms output readings The band is represented as a percentage of FS and can be set between 0 00 OFF and 1 00 and also...

Страница 15: ...xt character when in edit mode Move edit field selection up Move edit field selection down Zero Go to edit mode for currently selected field j Factory Defaults Confirmation Screen If Factory Defaults...

Страница 16: ...ote for TCP streaming to work a TCP connection on port 101 must be pre established the unit does not data stream over the HTTP port 80 5 2 Live data The live data page is the first page the user will...

Страница 17: ...is the maximum Voltage output of the transducer Source is where the setpoint is referenced from Internal will output the number entered as the setpoint value and Slave will output a percentage of the...

Страница 18: ...in the image above the input must get to Trip point 2 of fullscale and the relay will not switch off until the input drops to Trip point 2 of fullscale The trip point is the Engineering unit at which...

Страница 19: ...c command query query identification p parameter separated by commas if more than one The first letter to be entered on the command line before any command or query is the address identifier The is a...

Страница 20: ...rrect invalid parameters e ERROR if there was some internal comms error w BUSY if the comms is currently busy 6 3 Main commands a Output current readings r This command tells the CCD to get the curren...

Страница 21: ...n decided that when 100ms repeated output is used the data will be taken every 100ms and buffered up to be sent out every 500ms in blocks of 5 readings This has proven to be a more robust output metho...

Страница 22: ...command above is not non volatile This command can be used to set an initial setpoint value on system startup It takes one parameter which is the initial setpoint value The current value of the setpoi...

Страница 23: ...IP address To retrieve the current IP address use the query eip The returned data is IP ADDRESS xxx xxx xxx xxx where xxx is always a three digit octet b Ethernet subnet mask esm This command changes...

Страница 24: ...The number of decimal places passed in the range value dictates the number of decimal places shown for the main data output up to a max of 4 decimal places any more will get chopped off The current ra...

Страница 25: ...buffer size in seconds between 0 and 6 seconds 0 can be used to effectively turn the adaptive filtering off To retrieve the current filter size use the query fls The returned data is FILTERING SIZE x...

Страница 26: ...nction although it can take an optional parameter of 0 which clears any value already generated by a previous rezero To find the current user rezero value use the query irz The data returned is as fol...

Страница 27: ...Scale Voltage Each device attached to the CCD will have a full scale voltage which is the maximum voltage the device should output under normal operating conditions Typical values are 10V 5V and 1V Th...

Страница 28: ...ltage is 0 25V b Setpoint Source The setpoint source dictates where the setpoint value comes from assuming the mode is set to Auto see above This can be one of two possibilities Internal or Slave Inte...

Страница 29: ...of the filtering irrespective of the band setting It should be noted that this type of adaptive filtering can cause readings to be displayed abnormally particularly if the buffer size is one of the l...

Страница 30: ...within the instrument means that the user is strictly forbidden from removing the covers without invalidating Chell s obligations under both Warranty and COSSH 8 4 Cleaning A dirty instrument may be...

Страница 31: ...as Comma separated string returned See Table 3 for actual settings Ethernet IP address eip eip IP octets P1 xxx xxx xxx xxx Ethernet subnet mask esm esm IP octets P1 xxx xxx xxx xxx Input channel unit...

Страница 32: ...Range 10 000 Input Channel Full Scale 10 000 V or 100 00 mV If millivolt option fitted Input Channel Display Precision 3 3 decimal places Input Channel User Rezero 0 0 No rezero set Setpoint Value 0...

Страница 33: ...byte 0 1 as for sps query initial value 8 char string representation of a float initial slave value 8 char string representation of a float initial mode 1 byte 0 2 as for sim query Adaptive filter ban...

Отзывы: