SWITCH POSITION
M W
kW
MEASUREMENT EXTENT
0.5...5.5 *...200 M
W
0...45 * ...500 k
W
TEST VOLTAGE
500 V DC constant (± 5%)
from a few volts to 650 V max.
ACCURACY
± 2.5% of the end of scale value
VALUE OF MEASUREMENT
CURRENT
£ 5 mA DC
1 mA constant
MEASUREMENT TIME
FOR CAPACITATIVE LOAD
0.5 s/ µF
DISCHARGE TIME
5 s/ µF
PERMITTED OVERLOAD
600 V AC and DC
TYPE OF PROTECTION
Over capacity components
Insulation resistance measurement (IMEG 500N)
* Approximate value corresponding to the automatic change of scale (when red light lit:
multiply the reading by 10 to get the result)
Use
■
Disconnect the part of the circuit to be checked from the energy source
■
Place the switch on the voltmeter position
■
Connect the instrument according to the diagram (red terminal to the earth to
measure insulation resistance
compared to the earth)
■
Check that the circuit is not live
(no movement of the needle)
■
Put the switch on an adequate
position
■
Turn the handle until the orange
coloured indicator on the right of
the instrument lights up
■
Read the value: if the red indicator
situated on the left of the instrument is lit multiply the reading by 10 to get the result
■
Allow the circuit to discharge (a few seconds) before disconnecting the instrument.
Switch on
M W
or
kW
position
Insulation resistance