ADVICE ON USE
■
At rest the needle should read zero on the voltmeter position: if not, reset
it by means of the central black screw (see descriptive diagram).
■
Connect the protective earth terminal (see descriptive diagram) to the
protective conductor (earth).
■
Do not connect the instrument to the terminals of a circuit in which the
voltage exceeds 600 V
■
Before measuring any resistance check that the circuit is not live (switch
to voltmeter position before connecting)
■
After each insulation resistance measurement, allow the circuit to discharge
(a few seconds) before disconnecting the instrument
IMEG 500N
Red
Black
0.2 A Fuse
Measurement terminals
Earth protection
terminal
Fold-away
handle
Mechanical zero
reset screw for the
galvanometer
Range switch to be retur-
ned to M
W
/ V position
after use
Orange coloured indicator when lit
signals that the magneto is being
correctly cranked ; in other words
showing the presence of a voltage
which may reach 500 V (M
W
range), or the presence of a 1 mA
current (k
W
range), or of a 5 mA
current (
W
range)
Red indicator, when lit:
multiply the reading by 10
to get the result (on M
W
,
k
W
,
W
scales)
Safety bar which serves
as a rest for the left hand
whilst the handle is turned