background image

 
5. Appendix 

Rev. 2 

5.

 

A

PPENDIX

 

General Maintenance 

To maintain optimum performance and minimize wear, fixtures should be cleaned frequently.  Usage and 
environment are contributing factors in determining frequency. As a general rule, fixtures should be cleaned at 
least twice a month. Dust build up reduces light output performance and can cause overheating. This can lead 
to reduced lamp life and increased mechanical wear. Be sure to power off fixture before conducting 
maintenance. 

 

Unplug fixture from power.  

 

Use a vacuum or air compressor and a soft brush to remove dust collected on external 
vents. 

 

Clean all glass when the fixture is cold with a mild solution of glass cleaner or Isopropyl 
Alcohol and a soft lint free cotton cloth or lens tissue.  

 

Apply solution to the cloth or tissue and drag dirt and grime to the outside of the lens.  

 

Gently polish optical surfaces until they are free of haze and lint.  

The cleaning of external optical lenses and/or mirrors must be carried out periodically to optimize light output. 
Cleaning frequency depends on the environment in which the fixture operates. Damp, smoky or particularly dirty 
surroundings can cause greater accumulation of dirt on the unit’s optics. Clean with soft cloth using normal 
glass cleaning fluid. Clean the external optics at least every 20 days. Clean the fixture at least every 30/60 
days. 

 

Always dry the parts carefully after cleaning them. 

 

Never spin a fan using compressed air. 

 

Power Linking 

You will need a serial data link to run light shows of one or more fixtures using a DMX controller or to run 
synchronized shows on two or more fixtures set to a master/slave operating mode. The combined number of 
channels required by all the fixtures on a serial data link determines the number of fixtures the data link can 
support.  

Fixtures on a serial data link must be daisy chained in one single line. To comply with the EIA-485 
standard, no more than 32 fixtures should be connected on one data link. Connecting more than 32 
fixtures on one serial data link without the use of a DMX optically-isolated splitter may result in 
deterioration of the digital DMX signal.  

Maximum recommended serial data link distance: 500 m (1640 ft)  
Maximum recommended number of fixtures on a serial data link: 32 

 

Setting the Starting Address 

This DMX mode enables the use of a universal DMX controller device. Each fixture requires a start address 
from 1~512. A fixture requiring one or more channels for control begins to read the data on the channel 
indicated by the start address. For example, a fixture that uses six DMX channels and was addressed to start 
on DMX channel 100, would read data from channels: 100, 101, 102, 103, 104, and 105. Choose start 
addresses so that the channels used do not overlap, and note the start address selected for future reference. If 
you are unfamiliar with DMX, download the DMX Primer from www.chauvetlighting.com. 

 

 

Содержание TRIDENT

Страница 1: ...L 33351 U S A 800 762 1084 954 929 1115 FAX 954 929 5560 www chauvetlighting com User Manual Snapshot Use on Dimmer Outdoor Use Sound Activated DMX Master Slave Auto ranging Power Supply Replaceable Fuse User Serviceable Duty Cycle ...

Страница 2: ...N 7 MASTER SLAVE 7 STANDALONE OPERATION 7 Automatic 7 Sound Active 7 Custom Program 8 DMX CHANNEL VALUES 8 DIP SWITCH VALUES 8 5 APPENDIX 9 GENERAL MAINTENANCE 9 POWER LINKING 9 SETTING THE STARTING ADDRESS 9 GENERAL TROUBLESHOOTING 10 RETURNS 11 CLAIMS 11 TECHNICAL SPECIFICATIONS 12 CONTACT US 12 CHAUVET 2012 All Rights Reserved Information and specifications in this User Manual are subject to ch...

Страница 3: ...te certain types of information from the regular text CONVENTION MEANING 10 A DIP switch to be configured Menu A key to be pressed on the fixture s control panel 1 512 A range of values 50 60 A set of values of which only one can be chosen Settings A menu option not to be modified for example showing the operating mode current status MENU Settings A sequence of menu options to be followed ON A val...

Страница 4: ...Do not operate fixture at temperatures higher than this In the event of a serious operating problem stop using the unit immediately Never try to repair the unit by yourself Repairs carried out by unskilled people can lead to damage or malfunction Please contact the nearest authorized technical assistance center Never connect the device to a dimmer pack Make sure the power cord is never crimped or ...

Страница 5: ...oduction 5 Rev 2 Product Overview Safety attachment point Hanging bracket Fuse holder Power in Power out DMX in DMX out DIP switches Microphone Microphone sensitivity adjustment knob Back Panel A Back Panel B ...

Страница 6: ...e The maximum quantity of fixtures that may be linked is 26 Mounting Orientation The Trident may be mounted in any safe position provided there is adequate room for ventilation Rigging Be sure that the structure can support the weight of the fixture Mount the product securely This may be done with a screw nut and bolt or a hanging clamp Be sure to also use a safety cable The hole in each bracket i...

Страница 7: ...which will allow 1 fixture to act as the master and control all of the other slave fixtures You must set both the master and the slave s fixtures to the correct mode for this operation They must also be connected using DMX cables in a daisy chain fashion Master Settings 1 Using the DIP switches set the master fixture to one of the following modes custom automatic or sound activated Slave Settings ...

Страница 8: ...r to rotate CW CCW at a preset speed This may not be altered Do not connect a DMX controller to the daisy chain for this operation DMX Channel Values CHANNEL VALUE FUNCTION 1 000 004 005 028 029 056 057 084 085 112 113 140 141 168 169 197 198 224 225 255 Color Selection no dimming Blackout Red Green Blue Green Blue Red Blue Red Green Red Green Blue 3 color chase 7 color chase 2 000 004 005 255 Str...

Страница 9: ...y 30 60 days Always dry the parts carefully after cleaning them Never spin a fan using compressed air Power Linking You will need a serial data link to run light shows of one or more fixtures using a DMX controller or to run synchronized shows on two or more fixtures set to a master slave operating mode The combined number of channels required by all the fixtures on a serial data link determines t...

Страница 10: ...ed DMX cables Check DMX cables Wrong polarity settings on the controller Check polarity switch settings on the controller Loose DMX cables Check cable connections Faulty DMX interface Replace DMX input Faulty Main PCB Replace Main PCB Loss of signal Non DMX cables Use only DMX compatible cables Bouncing signals Install terminator as suggested Long cable Low level signal Install amplifier right aft...

Страница 11: ...r double boxing are recommended CHAUVET reserves the right to use its own discretion to repair or replace product s If you are given an RMA please include the following information on a piece of paper inside the box 1 Your name 2 Your address 3 Your phone number 4 The RMA 5 A brief description of the symptoms Claims Damage incurred in shipping is the responsibility of the shipper therefore the dam...

Страница 12: ...le 155 THERMAL Maximum ambient temperature 104 F 40 C CONTROL PROGRAMMING Data input locking 3 pin XLR male socket Data output locking 3 pin XLR female socket Data pin configuration pin 1 shield pin 2 pin 3 Protocols DMX 512 USITT DMX Channels 3 ORDERING INFORMATION Trident TRIDENT WARRANTY INFORMATION Warranty 2 year limited warranty Contact Us World Wide General Information CHAUVET 5200 NW 108th...

Отзывы: