3. Setup
6
Rev. 2
3.
S
ETUP
AC Power
This fixture runs on 100~240 VAC, 50/60 Hz. Before powering on the unit, make sure the line voltage
to which you are connecting it is within the range of accepted voltages.
Always connect the fixture to a switched circuit. Never connect the fixture to a rheostat
(variable resistor) or dimmer circuit, even if the rheostat or dimmer channel is used only as a 0
to 100% switch.
To determine the power requirements for a particular fixture, see the label affixed to the back of the
fixture or refer to the Technical Specifications. A fixture’s listed current rating indicates its average
current draw under normal conditions.
Always connect the fixture to a circuit with a suitable electrical ground.
Power Linking
This fixture contains power linking via the edison outlet located next to the power input cable.
The maximum quantity of fixtures that may be linked is 26.
Mounting
Orientation
The Trident™ may be mounted in any safe position, provided there is adequate room for ventilation.
Rigging
Be sure that the structure can support the weight of the fixture. Mount the product securely. This may
be done with a screw, nut and bolt, or a hanging clamp. Be sure to also use a safety cable. The hole
in each bracket is 13 mm in size. When rigging consider routine maintenance and control panel
access. Please see the following steps for installation.
•
If the power link out is intended to be used with multiple fixture, take into account the length
of each power cable, and mount the fixtures close enough to one another to accommodate
for this.
•
When aiming the fixture, you may use the bracket adjustment knobs (2x). Loosen each
knob, adjust to the desired angle, and then tighten both knobs by turning clockwise. Do not
use tools for this step, as it may cause damage.
•
Safety cables must always be used.
Additional power
link out
Fixture 1
Fixture 2
Fixture 3