VENTILATION
In the United Kingdom no special ventilation bricks or vents are required into the room containing the appliance,
provided normal adventitious room ventilation exists. The installer must satisfy this point by carrying out a
mandatory spillage test.
In the Republic of Ireland permanent ventilation must comply with the rules in force
SECTION NINE To Install the Appliance (installation instructions)
EXAMINE FLUE / CHIMNEY
Check that the flue/chimney conforms to the required specifications as previously stated. Examine the condition
and carry out any remedial work. If the flue/chimney has been used for solid fuel or oil, it should be swept prior to
appliance installation. A smoke test must be carried out to check that satisfactory smoke clearance has been
established. If all the smoke is not drawn into the flue, pre-heat the flue with a blowtorch or similar and re-check. If
there is any uncertainty examine for the cause and, if necessary, seek expert advice.
CONNECTING THE GAS SUPPLY
Determine where the gas supply is to be connected to the appliance. This may be done from the front of the unit
from either the left or right side, or a concealed fitting from the rear.
GAS CONCEALED CONNECTION
If the supply is to be a concealed connection it would be advisable to route 8mm O/D half hard copper tube to the
rear right side of the fireplace opening, taking into account the requirements of BS 6891 1988 dealing with enclosed
pipes. Form the tube so that it enters the fire via the blind grommet at the rear of the appliance. A 8mm restrictor
elbow can be positioned under the burner assembly on the right-hand side connected to the gas supply pipe and its
outlet connected to the gas appliance.
Note: pipework in the opening of the fireplace to the rear of the appliance must be suitably wrapped in accordance
with the regulations.
GAS CONNECTION FROM THE FRONT
Connections may be made from the front of the appliance from either the left or right in 8-mm diameter pipe. If a
left-hand connection is required the tube should be routed behind the bezel plate under the gas control tap and
onto the inlet elbow. The inlet elbows should be rotated to the required position. A suitable isolating cock should
always be fitted in the supply feed to the fire to facilitate servicing.