Charles Isotransformer 93-IXFMR3/6-A Скачать руководство пользователя страница 9

LT–IXFMR36–1

9

 Charles Industries, Ltd. All rights reserved. Printed in the United States of America.

Choosing Mounting Location

After selecting a wiring method, the mounting location must be chosen. Like any piece of transformer operated
equipment, the IsoTransformer will produce a noticeable “hum” when it is energized, although not nearly as loud
as non-encapsulated transformers. Consideration should be given to not mounting the IsoTransformer in or im-
mediately adjacent to areas where you will prefer it quiet, such as sleeping quarters. Locations to avoid are under
bunks or on the opposite side of an uninsulated bulkhead immediately adjacent to the head of a bunk. The Iso-
Transformer should be mounted either vertically on a bulkhead with the access panel at the bottom or horizontally
on the deck in a protected area away from rain or spray. When mounted vertically the bottom must be at least 24
inches above the deck or other equipment to avoid damage from splash and to ensure adequate access to wiring
connections. The unit must be mounted in a secure location capable of supporting the full weight of approximately
60 pounds. Proper ventilation around the case is important. Allow at least six inches on all four sides of the unit
for air circulation and cooling. During normal operation the case of the IsoTransformer may reach high tempera-
tures. To avoid burns locate the IsoTransformer in an area where persons will not come in contact with the unit.

Four 

/

-inch holes, 

/

-inch (without cover) from each end of the IsoTransformer are provided for rigging and

hoisting the unit (Figure 4). With the cover on, use the holes located 2 

/

-inches from the front. Typically,

shackles are used for hoisting.

Access to Input and Output Terminal Blocks

Four 3/8-inch Holes for

Rigging and Hoisting

(two on each side)

Cord Grip Connectors

See Table 1

Figure 4.  IsoTransformer Access Openings

Do not store equipment on or next to transformer. This unit is designed to operate hot and must have
free air flow to prevent overheating or charring of adjacent materials.

WARNING – FIRE HAZARD

Choosing Mounting Hardware

As with any marine equipment, secure mounting is of utmost importance. You will need to provide four bolts or
screws to secure the unit. They must be a 

/

-inch in diameter. The screws or bolts you choose should be backed

with a flat washer and kept vibration-free with a split-ring lock washer. If using bolts, they must be secured on
both sides of the bulkhead and also backed with a washer or washer plate. If using screws, they should be at
least 1” long. All hardware must be corrosion-resistant stainless steel or cadmium-plated steel.

Содержание Isotransformer 93-IXFMR3/6-A

Страница 1: ... 1 Page 1 of 15 Charles Industries Ltd All rights reserved Printed in the United States of America 3 6 KVA Isotransformert INSTALLATION INSTRUCTIONS OWNER S MANUAL Model 93 IXFMR3 6 A SHORELINE ISOLATION TRANSFORMER Marine Group ...

Страница 2: ...an Isolation Transformer 6 Wired as a Polarization Transformer 8 Choosing Mounting Location 9 Choosing Mounting Hardware 9 Mounting the IsoTransformer 10 Choosing the Appropriate Wire Type and Gauge 10 Choosing Electrical Wiring Hardware 10 Overcurrent Protection 11 Making IsoTransformer Connections 11 Securing Covers 14 Applying Power 14 OPERATING THE ISOTRANSFORMER 14 Safety First 14 Proper Oper...

Страница 3: ...hore grounding conductor is connected to a shield that is wound between the primary shore and secondary boat transformer windings This shield assures isolation on the boat by providing a protective layer between primary and secondary windings with in the transformer In the unlikely event of a breakdown within the transformer the shield can withstand the fault current of a properly sized shore supp...

Страница 4: ...nited States Code USC and the Code of Federal Regulations CFR U S Coast Guard Regulations are available from the American Boat and Yacht Council listed above Note Installation of the IsoTransformer must be made in accordance with all applicable standards and regula tions Environmental Precaution The IsoTransformer is intended for installation inside an engine room or elsewhere inside the boat Make...

Страница 5: ...o install the IsoTransformer as a polarization transformer if desired The third meth od is not preferred because wiring the unit in the manner described circumvents the AC grounding conductor isolation between shore and boat power and may require the use of a galvanic isolator to reduce galvanic corro sion Note Figure 1 Figure 2 and Figure 3 are reprinted with permission from the American Boat and...

Страница 6: ...ying shore conductors Fuses shall not be used in lieu of the simultaneous trip de vices 120 Volt branch circuit breakers are permitted to use single pole breakers in the ungrounded current carrying conductors The secondary of the isolation transformer is grounded polarized on the boat The boat grounding system green conductor is connected from the metal case of the isolation transformer to all non...

Страница 7: ...re permitted to use single pole breakers in the ungrounded current carrying conductors The secondary of the isolation transformer is grounded polarized on the boat The boat grounding system green conductor is connected from the shield and metal case of the isolation transformer to all noncurrent carrying parts of the boat s AC electrical system including the engine negative terminal or its bus wit...

Страница 8: ...ing green conductor is connected from the shore power cable and the boat s power inlet directly to all noncurrent carrying parts of the AC electrical system including the transformer case and shield and to the engine terminal or its bus without interposing switches or overcurrent protection devices One current carrying condcutor of the transformer secondary is grounded on the boat and is designate...

Страница 9: ...n all four sides of the unit for air circulation and cooling During normal operation the case of the IsoTransformer may reach high tempera tures To avoid burns locate the IsoTransformer in an area where persons will not come in contact with the unit Four inch holes inch without cover from each end of the IsoTransformer are provided for rigging and hoisting the unit Figure 4 With the cover on use t...

Страница 10: ...he wiring compartment should be at the bottom to ensure proper cooling of the unit 2 Remove the IsoTransformer and drill four marked holes with the proper sized drill bit 3 Realign the IsoTransformer s mounting holes with the drilled holes and fasten the unit to the bulkhead with the appropriate mounting hardware 4 Firmly secure all mounting hardware Choosing the Appropriate Wire Type and Gauge Al...

Страница 11: ...ation by a circuit breaker on the primary shore sup ply circuit A two pole shore power main circuit breaker is required for the shore power line going into the Iso Transformer This should be rated at 30 amps 120 volts 3000 Ampere Interrupting Capacity AIC and be of the long time delay type A Ground Fault Protector GFP is necessary if a shore grounding conductor is not used Refer to Figure 2 This s...

Страница 12: ...gure 5 use a UL Recognized insulated 6 AWG butt connector for the SH shield connection Crimp and tape the connection When wiring as an Isolation Transformer with Primary Ground Fault Protection Figure 6 or as a Polarization Transformer Figure 7 use a UL Recognized ring or captive spade terminal for making the SH shield connection at the GND screw 8 Tighten the cord grip connectors 9 Reinstall the ...

Страница 13: ...r I N P U T O U T P U T Figure 6 Typical Wiring as an Isolation Transformer with Primary Ground Fault Protector Method 2 see Figure 2 for Electrical Diagram H1 H2 SH GND X1 INPUT OUTPUT BLACK WHITE GREEN WHITE BLACK Line Neutral Neutral Line WHITE BLACK GREEN WHITE with STRIPE BLACK with STRIPE Shore Grounding GREEN Boat Grounding X2 Wire is fed through the cord grip connector I N P U T O U T P U ...

Страница 14: ...than periodic cleaning of the outside cabi net with a dry cloth and inspecting all connections for tightness and corrosion by a qualified service person TROUBLESHOOTING If there is a problem with the IsoTransformer first check that all connections are accurate and secure and retest If all connections are good contact Charles Marine Products for technical assistance WARRANTY CUSTOMER SERVICE Warran...

Страница 15: ...e is needed contact Charles Marine Products at 847 806 6300 Customer Service 847 806 6231 FAX For correspondence only mail to Charles Marine Products Charles Center 5600 Apollo Drive Rolling Meadows IL 60008 4049 SPECIFICATIONS The specifications for the IsoTransformer are listed in Table 2 Table 2 IsoTransformer Specifications Feature Specification Input Voltage 120 VAC Input Current 30 Amps Outp...

Отзывы: