Password mismatch
Displayed when passwords entered during setup do not
match.
Save and Cancel Settings
Select Save to store your settings to the smart memory button
and make your settings active. Select Cancel to revert back to
previously stored settings.
Note: Initial setup changes “Cancel” to “Re−enter Data”
Remote Display Operation
The Remote Display is identical in operation and displays the same information as on the charger. Use either the
buttons on the charger or the remote display to control the charger.
The remote display may be plugged in at any time. Should the logo screen be missing or some small blocks ap-
pear incorrect on the display, they will be corrected within 4 minutes of normal operation of the main screens
(Logo Screen, Temperature Screen, Battery Voltage Screen).
Lamp Test Mode
Press and hold the LAMP TEST button to verify the operation of the following:
Display will flash
Alarm will sound
Alarm relay will change to FAIL state. Use this mode to help verify alarm wiring
Blower will turn on.
Release the LAMP TEST button to cease testing.
During the Lamp Test, the DC output to the batteries is not affected.
Note:
Lamp Test is not available in Setup Mode.
Cooling and Blower Operation
The IMC Series
™
requires sufficient airflow for cooling to maintain operation. This is especially important on the
air vents, located on the bottom of the charger. Failure to allow sufficient airflow will cause the charger to over-
heat and shutdown.
The internal cooling blower is temperature controlled and will turn on and off as needed.