ZONE2 HEATING PARAMETERS (with accessory Expansion Unit)
P11
1000
*
Operating mode (0= Frost Protection, 1=Timed, 3=T.comfort)
°C
3
P12
1010
*
Comfort room temperature
°C
20
P13
1012
*
Reduced room temperature
°C
16
P14
1020
*
“Kt” curve slope
-
1,5
P15
1021
*
“Kt” curve drift
-
0
P16
1026
*
“Kt” curve adaptation (0=off)
-
1
P17
1040
Flow temperature setpoint (minimum value)
°C
25
P18
1041
Flow temperature setpoint (maximum value)
°C
80
P19
1042
*
Enable modulating temperature if set = “---” (flow temp. setpoint if P63=0)
°C
80
P20
1050
*
Room influence (“---” = disabled)
%
50
P21
1134
*
Opening/Closing speed of mix valve
s
30
DHW PARAMETERS
P22
1620
Operating mode in DHW (with Remote Control)
-
2
0=always enabled, 1=according to hourly heating programme,
2= according to hourly DHW programme.
P23
1640
Anti-legionella function Disabled
-
0
0=disabled, 1=periodic (depending on P24)
P24
1641
Periodic anti-legionella function enable (only if P23 =1)
-
7
1=daily, 2..6=intervals of 2..6 days, 7=once a week
P25
1663
Circulation temperature setpoint (additional DHW pump)
°C
45
P26
5470
Preheating time for DHW circuit (1=10’ -- 144=1440’)
min
0
BOILER PARAMETERS
P27
2243
Minimum boiler off time
min
3
P28
2217
Frost Protection setpoint
°C
5
P29
2250
Pump post-circulation time
min
3
P30
2441
Max. fan speed (heating)
rpm
xxx
P31
2455
Minimum boiler off differential
°C
5
P32
2720
Not used (Do NOT change this parameter)
-
0
P33
2721
Not used (Do NOT change this parameter)
-
1
SOLAR PLANT PARAMETERS (with accessory Expansion Unit)
P34
3810
Temperature - on differential
°C
8
P35
3811
Temperature - off differential
°C
4
P36
3830
Pump start function (“---” = disabled)
min
---
P37
3850
Solar panel manifold overheating protection (“---“ = disabled)
°C
---
P38
5050
DHW boiler tank charging temperature max
°C
65
P39
5051
Maximum temperature of storage tank
°C
90
CONFIGURATION
P40
5700
Not used (Do NOT change this parameter)
-
---
P41
5710
Zone 1 heating circuit (1=enabled)
-
1
P42
5715
Zone 2 heating circuit (1=enabled)
-
0
P43
5730
DHW sensor (1=Tank sensor, 2=Thermostat, 3=instantaneous sensor)
1
P44
5890
Not used (Do NOT change this parameter)
-
39
P45
5931
*
BX2 sensor input (first auxiliary sensor – section 11)
-
0
P46
5932
*
BX3 sensor input (second auxiliary sensor – section 11)
-
0
P47
5977
*
Input H5 (multifunction input – 18=Room thermostat)
-
18
P48
6020
*
Configuration of accessory Expansion Unit
-
0
P49
6024
Input EX21 module 1 (configuration of HC Safety Thermostat)
-
0
P50
6046
Input H2 module 1 (multifunction input)
-
0
P51
6097
Sensor type collector (1= NTC, 2= Pt 1000)
-
2
P52
6110
Building time constant
h
15
P53
6220
Software version
-
---
P54
6600
LPB device address
-
1
P55
6601
LPB segment address
-
0
P56
6640
Clock time source
-
0
MAINTENANCE
P57
7045
Time after maintenance
month
xxx
P58
6704
View/Hide secondary fault internal code (0=no)
-
1
BURNER CONTROL
P59
9512
Required ignition speed
rpm
xxx
P60
9524
Required minimum operating speed (low speed)
rpm
xxx
P61
9529
Required maximum operating speed (high speed)
rpm
xxx