201001 - 5500W WIRELESS REMOTE START INVERTER GENERATOR
TROUbLESHOOTING
36
Problem
Cause
Solution
Engine is running but no AC output.
Poor cord connection.
Check all connections.
Circuit breaker is open.
Reset circuit breaker. Check all circuit breakers.
Faulty brush assembly.
Replace brush assembly (Service Center).
Loose wiring.
Inspect and tighten wiring connections.
AC Overload: Button illuminated red
Reduce AC load and press Overload Reset Button
until illuminated green.
Other.
Contact the help line.
Engine hunts or falters.
Engine governor defective.
Contact the help line.
Dirty fuel valve.
Clean the fuel valve.
Carburetor is dirty and running lean.
Contact the help line.
Choke in wrong position.
Move choke until it stops under RUN position or
push in completely.
Repeated circuit breaker tripping.
Overload.
Review load and adjust. See “Connecting
Electrical Loads.”
Faulty power cords or device.
Check for damaged, bare or frayed wires. Replace
defective device.
Circuit breaker still too hot.
Let unit sit for 5 mins.