OWNER'S MANUAL

MODELS:

LGJ & MGJ

INDUSTRIAL DUTY DOOR OPERATOR

NOT FOR RESIDENTIAL USE

LISTED  DOOR  OPERATOR

41B6

Serial # 

(located on electrical box cover)

Installation Date

Wiring Type

2  YEAR  WARRANTY

c 2003, The Chamberlain Group, Inc.

All rights Reserved

MGJ CONTROL CONNECTION DIAGRAM

01-11452H

OPEN TIMER TO CLOSE

3 BUTTON STATION or 3 POSITION KEYSWITCH w/ SPRING RETURN TO CENTER AND STOP BUTTON

2 OR MORE

KEY LOCKOUT

R1

R2

R3

1

2

3

4

Stop

Close

Open

Stop

Close

Open

1

2

3

4

Stop

Close

Open

2 BUTTON STATION or 3 POSITION KEYSWITCH w/ SPRING RETURN TO CENTER

STANDARD

1

2

4

Close

Open

ALL CONTROL WIRING TYPES

2 OR MORE

1

2

4

Close

Open

Close

Open

OPEN / CLOSE

3

7

RADIO CONTROL

1 BUTTON STATION or

ANY AUXILIARY DEVICE

RESIDENTIAL RADIO CONTROLS

SENSING DEVICE TO REVERSE OR STOP

EXTERNAL INTERLOCK

3

10

4

5

4

5

Remove Jumper

When Interlock is Used

ONE

2 OR MORE

STANDARD

1

2

3

4

Stop

Close

Open

IMPORTANT NOTES:

1)   The 3-Button Control Station provided must be connected for operation.
2)   If a STOP button is not used, a jumper must be placed between termianls 3 and 4.
3)   Auxiliary control equipment may be any normally open two wire device such as
      pullswitch,  single button, loop detector, card key or such device.

Keyswitch

Sensing Device

ALL CONTROL WIRING TYPES

B2 or T1

WIRING TYPES ONLY

ALL CONTROL WIRING TYPES

T1 WIRING - RADIO TO OPEN ONLY

*

*

EXTERNAL

TERMINAL BLOCK

ALL CONTROL WIRING TYPES

ALL CONTROL WIRING TYPES

ALL CONTROL WIRING TYPES

TIMER TO CLOSE w/ WARNING LIGHT

ALL CONTROL WIRING TYPES

T1 CONTROL WIRING ONLY

11

12

Timer Defeat

Switch

13

14

Power Supply for

Warning Light

Auxiliary Terminal Block

Warning Light will activate 15 sec. before door closes.

ALL CONTROL WIRING TYPES

ATTENTION ELECTRICIAN:

USE 16 GAUGE OR HEAVIER WIRE

FOR ALL CONTROL CIRCUIT WIRING.

SEE NOTE #2

SEE NOTE #2

SEE NOTES

#2 AND #3

(Refer to page 15 for model LGJ control connections)

Содержание MGJ

Страница 1: ... Interlock is Used ONE 2 OR MORE STANDARD 1 2 3 4 Stop Close Open IMPORTANT NOTES 1 The 3 Button Control Station provided must be connected for operation 2 If a STOP button is not used a jumper must be placed between termianls 3 and 4 3 Auxiliary control equipment may be any normally open two wire device such as pullswitch single button loop detector card key or such device Keyswitch Sensing Devic...

Страница 2: ...ERSING EDGE IS STRONGLY RECOMMENDED FOR ALL COMMERCIAL OPERATOR INST ALLA TIONS REQUIRED WHEN THE 3 BUTTON CONTROL STATION IS OUT OF SIGHT OF DOOR OR ANY OTHER CONTROL AUTOMATIC OR MANUAL IS USED SPECIFICATIONS ELECTRICAL TRANSFORMER 24VAC CONTROL STATION NEMA 1 three button station OPEN CLOSE STOP WIRING TYPE MGJ B2 C2 Factory Shipped LGJ G2 Factory Shipped See pages 13 and 14 for optional contro...

Страница 3: ...ur unit If necessary model MGJ may also be field modified to accommodate opposite handing Refer to the conversion instructions below and on page 4 REPLACEMENT PART LISTS MODEL MGJ Refer to the parts lists below for replacement kits available for your operator If optional modifications and or accessories are included with your operator certain components may be added or removed from these lists Ind...

Страница 4: ... Switch Direction Locate Switch 1 on PCB in the electrical box Place pole 2 of Switch 1 in the OFF position With this setting limit switch labeled A is the close switch limit switch labeled B is the open switch IMPORTANT Refer to page 9 for for complete instructions on setting of limit switches 3 Affix Electrical Box Cover Caution Label Place the caution label on electrical box cover such that the...

Страница 5: ... 2 2 1 1 2 1 1 1 2 4 8 2 8 4 2 Description Reversing Contactor See Notes Electrical Box Cover Electrical Box Capacitor Clamp See Notes Transformer 24V DPDT Relay Capacitor 7MFD See Notes Resistor 20 Ohm Terminal Block Assy 3 Lug 10 Position Terminal Block MGJ Limit Shaft 3 8 Bearing Plastic Flange Limit Nut Sprocket 48B07 Washer Shim 3 8 I D x 01 Flatwasher 3 8 Roll Pin 1 8 Dia x 3 4 Long E Ring 3...

Страница 6: ...s time 2 Wrap drive chain around door sprocket and join roller chain ends together with master link 3 Raise operator to approximate mounting position and position chain over operator sprocket 4 Raise or lower operator until the chain is slightly taut not tight Make sure the operator output shaft is parallel to door shaft and sprockets are aligned When in position secure the operator to wall or mou...

Страница 7: ...Support Bracket Mounting Bracket LH Mounting Bracket RH Gear Reducer 40 1 Electrical Box Motor Nut Stud 1 1 1 1 1 1 1 1 10 11397 10 11389 1 10 11398 2 32 11435 See Page 16 See Page 16 84 FN 10 84 FN 19144 EMERGENCY MANUAL OPERATION This operator a floor level disconnect chain to disconnect the door from the door operator allowing for manual operation of the door in case of emergency or power failu...

Страница 8: ...rdance with local codes ENTRAPMENT PROTECTION ACCESSORIES OPTIONAL IT IS STRONGLY RECOMMENDED THAT A SENSING EDGE OR OTHER ENTRAPMENT PROTECTION DEVICE BE USED IN CONJUNCTION WITH THIS OPERATOR TAKE UP REEL Take up reel should be installed 12 above the top of the door COIL CORD Connect operator end of coil cord to junction box not supplied fastened to the wall approximately halfway up the door ope...

Страница 9: ...over on the electrical enclosure and locate dip switch SW1 on circuit board The direction of the limit travel is determined by the switch SW1 pole 2 setting If your operator is mounted Motor Side Up Set dip switch SW1 pole 2 to ON position If your operator is mounted Motor Side Down Set dip switch SW1 pole 2 to OFF position NOTE See Mounting Options on page 5 to verify the correct mounting applica...

Страница 10: ...aximum run time is 45 seconds MAXIMUM RUN TIME 2 ON CLOSE limit switch B OFF CLOSE limit switch A MAXIMUM RUN TIME 3 OFF DO NOT ADJUST 4 OFF DO NOT ADJUST CONSULT FACTORY FOR ADJUSTEMENT SWITCH 1 SETTINGS SWITCH 2 SETTINGS TIMER TO CLOSE SWITCH SETTING O ON F OFF 1 2 3 4 O O O O F O O O O F O O F F O O O O F O F O F O O F F O F F F O 1 2 3 4 O O O F F O O F O F O F F F O F O O F F F O F F O F F F ...

Страница 11: ... Control Station WARNING Notice Push Buttons IMPORTANT Mount WARNING NOTICE beside or below the push button station MOUNT WARNING NOTICE DETERMINE WIRING TYPE Refer to the wiring diagram located on the inside cover the electrical box to determine the type of control wiring SPECIAL CONTROL WIRING If your operator was shipped from the factory with non standard control wiring or with optional accesso...

Страница 12: ...SE LIMIT SWITCH NC C 1 7 10 OPEN SAFETY EDGE OPEN CLOSE LIMIT SWITCH AUX OPEN C NO NC LIMIT SWITCH NC C TO MOTOR POWER IN L1 3 PHASE INTERLOCK OP R1 OP OP CL CL OP CL OP 14 13 IN MOTOR R1 OPEN CLOSE R2 R1 OPEN CLOSE 2 14 13 CL CL LIMIT SWITCH NC CLOSE C R1 BK BK BK BRN BR YEL OR OR OR OR RED RED OR YEL YEL PUR OR PUR PUR PUR PUR PUR R3 RED BRN YEL OR OR SEE NOTE 1 RED WHEN PRESENT 230V BRAKE GY GY...

Страница 13: ...SE LIMIT SWITCH NC C 1 7 10 OPEN SAFETY EDGE OPEN CLOSE LIMIT SWITCH AUX OPEN C NO NC LIMIT SWITCH NC C TO MOTOR POWER IN L1 3 PHASE INTERLOCK OP R1 OP OP CL CL OP CL OP 14 13 IN MOTOR R1 OPEN CLOSE R2 R1 OPEN CLOSE 2 14 13 CL CL LIMIT SWITCH NC CLOSE C R1 BK BK BK BRN BR YEL OR OR OR OR RED RED OR YEL YEL PUR OR PUR PUR PUR PUR PUR R3 RED BRN YEL OR OR SEE NOTE 1 RED WHEN PRESENT 230V BRAKE GY GY...

Страница 14: ... Control Station WARNING Notice Push Buttons IMPORTANT Mount WARNING NOTICE beside or below the push button station MOUNT WARNING NOTICE DETERMINE WIRING TYPE Refer to the wiring diagram located on the inside cover the electrical box to determine the type of control wiring SPECIAL CONTROL WIRING If your operator was shipped from the factory with non standard control wiring or with optional accesso...

Страница 15: ...aximum run time is 45 seconds MAXIMUM RUN TIME 2 ON CLOSE limit switch B OFF CLOSE limit switch A MAXIMUM RUN TIME 3 OFF DO NOT ADJUST 4 OFF DO NOT ADJUST CONSULT FACTORY FOR ADJUSTEMENT SWITCH 1 SETTINGS SWITCH 2 SETTINGS TIMER TO CLOSE SWITCH SETTING O ON F OFF 1 2 3 4 O O O O F O O O O F O O F F O O O O F O F O F O O F F O F F F O 1 2 3 4 O O O F F O O F O F O F F F O F O O F F F O F F O F F F ...

Страница 16: ...n the electrical enclosure and locate dip switch SW1 on circuit board The direction of the limit travel is determined by the switch SW1 pole 2 setting If your operator is mounted Motor Side Up Set dip switch SW1 pole 2 to ON position If your operator is mounted Motor Side Down Set dip switch SW1 pole 2 to OFF position NOTE See Mounting Options on page 5 to verify the correct mounting application A...

Страница 17: ...rdance with local codes ENTRAPMENT PROTECTION ACCESSORIES OPTIONAL IT IS STRONGLY RECOMMENDED THAT A SENSING EDGE OR OTHER ENTRAPMENT PROTECTION DEVICE BE USED IN CONJUNCTION WITH THIS OPERATOR TAKE UP REEL Take up reel should be installed 12 above the top of the door COIL CORD Connect operator end of coil cord to junction box not supplied fastened to the wall approximately halfway up the door ope...

Страница 18: ...Support Bracket Mounting Bracket LH Mounting Bracket RH Gear Reducer 40 1 Electrical Box Motor Nut Stud 1 1 1 1 1 1 1 1 10 11397 10 11389 1 10 11398 2 32 11435 See Page 16 See Page 16 84 FN 10 84 FN 19144 EMERGENCY MANUAL OPERATION This operator a floor level disconnect chain to disconnect the door from the door operator allowing for manual operation of the door in case of emergency or power failu...

Страница 19: ...s time 2 Wrap drive chain around door sprocket and join roller chain ends together with master link 3 Raise operator to approximate mounting position and position chain over operator sprocket 4 Raise or lower operator until the chain is slightly taut not tight Make sure the operator output shaft is parallel to door shaft and sprockets are aligned When in position secure the operator to wall or mou...

Страница 20: ... 2 2 1 1 2 1 1 1 2 4 8 2 8 4 2 Description Reversing Contactor See Notes Electrical Box Cover Electrical Box Capacitor Clamp See Notes Transformer 24V DPDT Relay Capacitor 7MFD See Notes Resistor 20 Ohm Terminal Block Assy 3 Lug 10 Position Terminal Block MGJ Limit Shaft 3 8 Bearing Plastic Flange Limit Nut Sprocket 48B07 Washer Shim 3 8 I D x 01 Flatwasher 3 8 Roll Pin 1 8 Dia x 3 4 Long E Ring 3...

Страница 21: ... Switch Direction Locate Switch 1 on PCB in the electrical box Place pole 2 of Switch 1 in the OFF position With this setting limit switch labeled A is the close switch limit switch labeled B is the open switch IMPORTANT Refer to page 9 for for complete instructions on setting of limit switches 3 Affix Electrical Box Cover Caution Label Place the caution label on electrical box cover such that the...

Страница 22: ...ur unit If necessary model MGJ may also be field modified to accommodate opposite handing Refer to the conversion instructions below and on page 4 REPLACEMENT PART LISTS MODEL MGJ Refer to the parts lists below for replacement kits available for your operator If optional modifications and or accessories are included with your operator certain components may be added or removed from these lists Ind...

Страница 23: ...ERSING EDGE IS STRONGLY RECOMMENDED FOR ALL COMMERCIAL OPERATOR INST ALLA TIONS REQUIRED WHEN THE 3 BUTTON CONTROL STATION IS OUT OF SIGHT OF DOOR OR ANY OTHER CONTROL AUTOMATIC OR MANUAL IS USED SPECIFICATIONS ELECTRICAL TRANSFORMER 24VAC CONTROL STATION NEMA 1 three button station OPEN CLOSE STOP WIRING TYPE MGJ B2 C2 Factory Shipped LGJ G2 Factory Shipped See pages 13 and 14 for optional contro...

Страница 24: ... Interlock is Used ONE 2 OR MORE STANDARD 1 2 3 4 Stop Close Open IMPORTANT NOTES 1 The 3 Button Control Station provided must be connected for operation 2 If a STOP button is not used a jumper must be placed between termianls 3 and 4 3 Auxiliary control equipment may be any normally open two wire device such as pullswitch single button loop detector card key or such device Keyswitch Sensing Devic...

Отзывы: