SINGLE PHASE SCHEMATIC DIAGRAM for LGJ

1666

CONTROL WIRING

Standard C2 or B2 Wiring

Model MGJ operators are shipped from the factory
with jumper set for C2 wiring, which requires constant
pressure on button to close the door.  If momentary
contact in close direction is desired (B2 wiring) you
must include an entrapment protection device.  See
close control jumper setting below.

Constant pressure on close (C2 wiring)

Red jumper wire was placed on terminal #2 in 
the electrical enclosure.  The operator will require 
constant pressure on close control in order to keep
door moving in the close direction.

Momentary contact on close (B2 wiring)

Move red jumper wire from terminal #2 to terminal 
#3. The operator will require only momentary 
contact to close the door.

LOCATING THE CONTROL STATION

All operators are supplied with some type of control station. Generally a three button station
(OPEN/CLOSE/STOP) is provided. A two-position key switch or control station (OPEN/CLOSE) may be added or
substituted when requested at the time of  order. Mount the control station near the door.

WARNING

CAUTION

WARNING

WARNING

INSTALL THE CONTROL STATION WHERE THE

DOOR IS VISIBLE, BUT AWAY FROM THE DOOR AND

ITS HARDWARE. IF CONTROL STATION CANNOT BE

INSTALLED WHERE DOOR IS VISIBLE, OR IF ANY

DEVICE OTHER THAN THE CONTROL STATION IS

USED TO ACTIVATE THE DOOR, 

A REVERSING

EDGE MUST BE INSTALLED ON THE BOTTOM OF

THE DOOR.

FAILURE TO INSTALL A REVERSING

EDGE UNDER THESE CIRCUMSTANCES MAY

RESULT IN SERIOUS INJURY OR DEATH TO

PERSONS TRAPPED BENEATH THE DOOR.

W A R N I N G

TO PREVENT ENTRAPMENT

DO NOT START DOOR  DOWNWARD

UNLESS DOORWAY IS CLEAR

OPEN

CLOSE

STOP

Control Station

WARNING Notice

Push

Buttons

IMPORTANT

: Mount WARNING NOTICE beside or

below the push button station.

MOUNT WARNING NOTICE

DETERMINE WIRING TYPE

Refer to the wiring diagram located on the inside cover the electrical box to determine the type of control wiring. 

SPECIAL CONTROL WIRING

If your operator was shipped from the factory with
non-standard control wiring or with optional
accessories that require additional instructions, refer
to the wiring diagram(s) indicated in the special
control wiring data box.  When a replacement wiring
diagram is present, wiring diagrams in this manual
will not apply.  Refer only to the replacement wiring
diagram for all connections.

IMPORTANT NOTE:  If your wiring diagram is
missing, or you are unsure of the wiring type for
your operator, contact the customer service
department @ 1-800-528-2806.

MODEL MGJ

Standard G2 Wiring

Model LGJ operators are supplied with type G2 control
wiring.  Study the control features list below to
determine the features and type of control equipment
that may be used with your operator.

Entry Controls:

OPEN control requiring maintained contact.
OPEN control requiring only momentary contact.
CLOSE control requiring maintained contact.
CLOSE control requiring only momentary contact.
OPEN/CLOSE single control requiring momentary
contact..
STOP control requiring momentary contact.

Safety Devices:

External Interlock switch to disable all control
pneumatic safety (N.C.) to STOP while closing Safety
Device to REVERSE while closing Door Lock Sensing
Circuit.

Operational Features:

REVERSE (if closing) with momentary contact on
OPEN.
AUTOMATIC TIMER to CLOSE from any device.
AUTOMATIC TIMER to CLOSE from selected devices.
DELAY REVERSE in either direction for 1 second.
STOP after maximum run time is exceeded.

Note:

Refer to LGJ control connection diagrams on page 15.

MODEL LGJ

Содержание MGJ

Страница 1: ... Interlock is Used ONE 2 OR MORE STANDARD 1 2 3 4 Stop Close Open IMPORTANT NOTES 1 The 3 Button Control Station provided must be connected for operation 2 If a STOP button is not used a jumper must be placed between termianls 3 and 4 3 Auxiliary control equipment may be any normally open two wire device such as pullswitch single button loop detector card key or such device Keyswitch Sensing Devic...

Страница 2: ...ERSING EDGE IS STRONGLY RECOMMENDED FOR ALL COMMERCIAL OPERATOR INST ALLA TIONS REQUIRED WHEN THE 3 BUTTON CONTROL STATION IS OUT OF SIGHT OF DOOR OR ANY OTHER CONTROL AUTOMATIC OR MANUAL IS USED SPECIFICATIONS ELECTRICAL TRANSFORMER 24VAC CONTROL STATION NEMA 1 three button station OPEN CLOSE STOP WIRING TYPE MGJ B2 C2 Factory Shipped LGJ G2 Factory Shipped See pages 13 and 14 for optional contro...

Страница 3: ...ur unit If necessary model MGJ may also be field modified to accommodate opposite handing Refer to the conversion instructions below and on page 4 REPLACEMENT PART LISTS MODEL MGJ Refer to the parts lists below for replacement kits available for your operator If optional modifications and or accessories are included with your operator certain components may be added or removed from these lists Ind...

Страница 4: ... Switch Direction Locate Switch 1 on PCB in the electrical box Place pole 2 of Switch 1 in the OFF position With this setting limit switch labeled A is the close switch limit switch labeled B is the open switch IMPORTANT Refer to page 9 for for complete instructions on setting of limit switches 3 Affix Electrical Box Cover Caution Label Place the caution label on electrical box cover such that the...

Страница 5: ... 2 2 1 1 2 1 1 1 2 4 8 2 8 4 2 Description Reversing Contactor See Notes Electrical Box Cover Electrical Box Capacitor Clamp See Notes Transformer 24V DPDT Relay Capacitor 7MFD See Notes Resistor 20 Ohm Terminal Block Assy 3 Lug 10 Position Terminal Block MGJ Limit Shaft 3 8 Bearing Plastic Flange Limit Nut Sprocket 48B07 Washer Shim 3 8 I D x 01 Flatwasher 3 8 Roll Pin 1 8 Dia x 3 4 Long E Ring 3...

Страница 6: ...s time 2 Wrap drive chain around door sprocket and join roller chain ends together with master link 3 Raise operator to approximate mounting position and position chain over operator sprocket 4 Raise or lower operator until the chain is slightly taut not tight Make sure the operator output shaft is parallel to door shaft and sprockets are aligned When in position secure the operator to wall or mou...

Страница 7: ...Support Bracket Mounting Bracket LH Mounting Bracket RH Gear Reducer 40 1 Electrical Box Motor Nut Stud 1 1 1 1 1 1 1 1 10 11397 10 11389 1 10 11398 2 32 11435 See Page 16 See Page 16 84 FN 10 84 FN 19144 EMERGENCY MANUAL OPERATION This operator a floor level disconnect chain to disconnect the door from the door operator allowing for manual operation of the door in case of emergency or power failu...

Страница 8: ...rdance with local codes ENTRAPMENT PROTECTION ACCESSORIES OPTIONAL IT IS STRONGLY RECOMMENDED THAT A SENSING EDGE OR OTHER ENTRAPMENT PROTECTION DEVICE BE USED IN CONJUNCTION WITH THIS OPERATOR TAKE UP REEL Take up reel should be installed 12 above the top of the door COIL CORD Connect operator end of coil cord to junction box not supplied fastened to the wall approximately halfway up the door ope...

Страница 9: ...over on the electrical enclosure and locate dip switch SW1 on circuit board The direction of the limit travel is determined by the switch SW1 pole 2 setting If your operator is mounted Motor Side Up Set dip switch SW1 pole 2 to ON position If your operator is mounted Motor Side Down Set dip switch SW1 pole 2 to OFF position NOTE See Mounting Options on page 5 to verify the correct mounting applica...

Страница 10: ...aximum run time is 45 seconds MAXIMUM RUN TIME 2 ON CLOSE limit switch B OFF CLOSE limit switch A MAXIMUM RUN TIME 3 OFF DO NOT ADJUST 4 OFF DO NOT ADJUST CONSULT FACTORY FOR ADJUSTEMENT SWITCH 1 SETTINGS SWITCH 2 SETTINGS TIMER TO CLOSE SWITCH SETTING O ON F OFF 1 2 3 4 O O O O F O O O O F O O F F O O O O F O F O F O O F F O F F F O 1 2 3 4 O O O F F O O F O F O F F F O F O O F F F O F F O F F F ...

Страница 11: ... Control Station WARNING Notice Push Buttons IMPORTANT Mount WARNING NOTICE beside or below the push button station MOUNT WARNING NOTICE DETERMINE WIRING TYPE Refer to the wiring diagram located on the inside cover the electrical box to determine the type of control wiring SPECIAL CONTROL WIRING If your operator was shipped from the factory with non standard control wiring or with optional accesso...

Страница 12: ...SE LIMIT SWITCH NC C 1 7 10 OPEN SAFETY EDGE OPEN CLOSE LIMIT SWITCH AUX OPEN C NO NC LIMIT SWITCH NC C TO MOTOR POWER IN L1 3 PHASE INTERLOCK OP R1 OP OP CL CL OP CL OP 14 13 IN MOTOR R1 OPEN CLOSE R2 R1 OPEN CLOSE 2 14 13 CL CL LIMIT SWITCH NC CLOSE C R1 BK BK BK BRN BR YEL OR OR OR OR RED RED OR YEL YEL PUR OR PUR PUR PUR PUR PUR R3 RED BRN YEL OR OR SEE NOTE 1 RED WHEN PRESENT 230V BRAKE GY GY...

Страница 13: ...SE LIMIT SWITCH NC C 1 7 10 OPEN SAFETY EDGE OPEN CLOSE LIMIT SWITCH AUX OPEN C NO NC LIMIT SWITCH NC C TO MOTOR POWER IN L1 3 PHASE INTERLOCK OP R1 OP OP CL CL OP CL OP 14 13 IN MOTOR R1 OPEN CLOSE R2 R1 OPEN CLOSE 2 14 13 CL CL LIMIT SWITCH NC CLOSE C R1 BK BK BK BRN BR YEL OR OR OR OR RED RED OR YEL YEL PUR OR PUR PUR PUR PUR PUR R3 RED BRN YEL OR OR SEE NOTE 1 RED WHEN PRESENT 230V BRAKE GY GY...

Страница 14: ... Control Station WARNING Notice Push Buttons IMPORTANT Mount WARNING NOTICE beside or below the push button station MOUNT WARNING NOTICE DETERMINE WIRING TYPE Refer to the wiring diagram located on the inside cover the electrical box to determine the type of control wiring SPECIAL CONTROL WIRING If your operator was shipped from the factory with non standard control wiring or with optional accesso...

Страница 15: ...aximum run time is 45 seconds MAXIMUM RUN TIME 2 ON CLOSE limit switch B OFF CLOSE limit switch A MAXIMUM RUN TIME 3 OFF DO NOT ADJUST 4 OFF DO NOT ADJUST CONSULT FACTORY FOR ADJUSTEMENT SWITCH 1 SETTINGS SWITCH 2 SETTINGS TIMER TO CLOSE SWITCH SETTING O ON F OFF 1 2 3 4 O O O O F O O O O F O O F F O O O O F O F O F O O F F O F F F O 1 2 3 4 O O O F F O O F O F O F F F O F O O F F F O F F O F F F ...

Страница 16: ...n the electrical enclosure and locate dip switch SW1 on circuit board The direction of the limit travel is determined by the switch SW1 pole 2 setting If your operator is mounted Motor Side Up Set dip switch SW1 pole 2 to ON position If your operator is mounted Motor Side Down Set dip switch SW1 pole 2 to OFF position NOTE See Mounting Options on page 5 to verify the correct mounting application A...

Страница 17: ...rdance with local codes ENTRAPMENT PROTECTION ACCESSORIES OPTIONAL IT IS STRONGLY RECOMMENDED THAT A SENSING EDGE OR OTHER ENTRAPMENT PROTECTION DEVICE BE USED IN CONJUNCTION WITH THIS OPERATOR TAKE UP REEL Take up reel should be installed 12 above the top of the door COIL CORD Connect operator end of coil cord to junction box not supplied fastened to the wall approximately halfway up the door ope...

Страница 18: ...Support Bracket Mounting Bracket LH Mounting Bracket RH Gear Reducer 40 1 Electrical Box Motor Nut Stud 1 1 1 1 1 1 1 1 10 11397 10 11389 1 10 11398 2 32 11435 See Page 16 See Page 16 84 FN 10 84 FN 19144 EMERGENCY MANUAL OPERATION This operator a floor level disconnect chain to disconnect the door from the door operator allowing for manual operation of the door in case of emergency or power failu...

Страница 19: ...s time 2 Wrap drive chain around door sprocket and join roller chain ends together with master link 3 Raise operator to approximate mounting position and position chain over operator sprocket 4 Raise or lower operator until the chain is slightly taut not tight Make sure the operator output shaft is parallel to door shaft and sprockets are aligned When in position secure the operator to wall or mou...

Страница 20: ... 2 2 1 1 2 1 1 1 2 4 8 2 8 4 2 Description Reversing Contactor See Notes Electrical Box Cover Electrical Box Capacitor Clamp See Notes Transformer 24V DPDT Relay Capacitor 7MFD See Notes Resistor 20 Ohm Terminal Block Assy 3 Lug 10 Position Terminal Block MGJ Limit Shaft 3 8 Bearing Plastic Flange Limit Nut Sprocket 48B07 Washer Shim 3 8 I D x 01 Flatwasher 3 8 Roll Pin 1 8 Dia x 3 4 Long E Ring 3...

Страница 21: ... Switch Direction Locate Switch 1 on PCB in the electrical box Place pole 2 of Switch 1 in the OFF position With this setting limit switch labeled A is the close switch limit switch labeled B is the open switch IMPORTANT Refer to page 9 for for complete instructions on setting of limit switches 3 Affix Electrical Box Cover Caution Label Place the caution label on electrical box cover such that the...

Страница 22: ...ur unit If necessary model MGJ may also be field modified to accommodate opposite handing Refer to the conversion instructions below and on page 4 REPLACEMENT PART LISTS MODEL MGJ Refer to the parts lists below for replacement kits available for your operator If optional modifications and or accessories are included with your operator certain components may be added or removed from these lists Ind...

Страница 23: ...ERSING EDGE IS STRONGLY RECOMMENDED FOR ALL COMMERCIAL OPERATOR INST ALLA TIONS REQUIRED WHEN THE 3 BUTTON CONTROL STATION IS OUT OF SIGHT OF DOOR OR ANY OTHER CONTROL AUTOMATIC OR MANUAL IS USED SPECIFICATIONS ELECTRICAL TRANSFORMER 24VAC CONTROL STATION NEMA 1 three button station OPEN CLOSE STOP WIRING TYPE MGJ B2 C2 Factory Shipped LGJ G2 Factory Shipped See pages 13 and 14 for optional contro...

Страница 24: ... Interlock is Used ONE 2 OR MORE STANDARD 1 2 3 4 Stop Close Open IMPORTANT NOTES 1 The 3 Button Control Station provided must be connected for operation 2 If a STOP button is not used a jumper must be placed between termianls 3 and 4 3 Auxiliary control equipment may be any normally open two wire device such as pullswitch single button loop detector card key or such device Keyswitch Sensing Devic...

Отзывы: