LISTED DOOR OPERATOR
41B6
LGJ CONTROL CONNECTION DIAGRAM
NUMBERED BOXES CORRESPOND WITH TERMINALS ON J1 CONNECTOR STRIP
If Neccessary, Remove The Connector Block From The Board To Secure Each Wire Connection
Connect field wires to any terminal number shown in the respective column. See control
options below for explanation of how field control will function for each terminal number.
OR
OR
OR
11
9
7
8
4
3
5
OPEN
CLOSE
STOP
STANDARD
3 BUTTON CONTROL
10
5
SENSING
EDGE
8
5
9
11
ANY OPEN
CONTROL
(SEE NOTE)
6
5
ANY
OPEN & CLOSE
CONTROL
(SEE NOTE)
OR
OR
OR
11
9
7
8
4
3
5
OPEN
CLOSE
STOP
OR
OR
OR
11
9
7
8
4
5
OPEN
CLOSE
STOP
OR
OR
OR
11
9
7
8
4
3
5
OPEN
CLOSE
STOP
OR
OR
11
4
5
OPEN
OFF
ON
CLOSE
2 BUTTON
CONTROL
(SEE NOTE)
3 BUTTON CONTROL
WITH
KEYED LOCK-OUT
3 BUTTON CONTROL
WITH
MULTIPLE CONTROL STATIONS
WHEN CONNECTING AN
OPEN CONTROL TO:
- Open control will require constant
pressure to keep door moving.
- Open control will only require
momentary contact and will set or
reset timer to close.
- Open control will only require
momentary contact and will NOT
set or reset timer to close.
WHEN CONNECTING AN
CLOSE CONTROL TO:
- Close control will require constant
pressure to keep door moving.
- Close control will only require
momentary contact.
DO NOT add unless using an
entrapment Protection device.
11
9
8
4
7
OPEN AND CLOSE CONTROL OPTIONS
IMPORTANT NOTE:
WHEN STOP BUTTON IS NOT USED, ADD A JUMPER FROM
TERMINAL 3 TO TERMINAL 5.
3
5
MAXIMUM RUN TIME:
1 - ON: Maximum run time is 90 seconds.
OFF: Maximum run time is 45 seconds.
MAXIMUM RUN TIME:
2 - ON: CLOSE limit switch B
OFF: CLOSE limit switch A
MAXIMUM RUN TIME:
3 - OFF: (DO NOT ADJUST)
4 - OFF: (DO NOT ADJUST)
CONSULT FACTORY FOR ADJUSTEMENT
SWITCH #1 SETTINGS
SWITCH #2 SETTINGS
TIMER TO CLOSE SWITCH SETTING:
O = ON F = OFF
1 2 3 4
O O O O
F O O O
O F O O
F F O O
O O F O
F O F O
O F F O
F F F O
1 2 3 4
O O O F
F O O F
O F O F
F F O F
O O F F
F O F F
O F F F
F F F F
= Disabled
= 2 sec
= 3 sec
= 13 sec
= 15 sec
= 23 sec
= 32.5 sec
= 43.6 sec
= 72 sec
= 88 sec
= 107 sec
= 126sec
= 148 sec
= 172 sec
= 198 sec
= 224 sec
SETTING
SETTING
TIME
TIME
SWITCH ADJUSTMENTS
OR
OR
Use SAE 30 Oil (Never use grease or silicone spray).
Repeat ALL procedures.
Do not lubricate motor. Motor bearings are rated for continuous operation.
Inspect and service whenever a malfunction is observed or suspected.
CAUTION: BEFORE SERVICING, ALWAYS DISCONNECT OPERATOR FROM POWER SUPPLY.
Check at the intervals listed in the following chart.
HOW TO ORDER REPAIR PARTS
OUR LARGE SERVICE ORGANIZATION
SPANS AMERICA
INSTALLATION AND SERVICE INFORMATION
ARE AVAILABLE 6 DAYS A WEEK
CALL OUR TOLL FREE NUMBER - 1-800-528-2806
HOURS 7:00 TO 3:30 p.m. (Mountain Std. Time)
MONDAY Through SATURDAY
WHEN ORDERING REPAIR PARTS
PLEASE SUPPLY THE FOLLOWING INFORMATION:
PART NUMBER DESCRIPTION MODEL NUMBER
ADDRESS ORDER TO:
THE CHAMBERLAIN GROUP, INC.
Electronic Parts & Service Dept.
2301 N. Forbes Blvd., Suite 104
Tucson, AZ 85745
EVERY
EVERY
EVERY
ITEM
PROCEDURE
3 MONTHS
6 MONTHS
12 MONTHS
Drive Chain
Check for excessive slack.
Check & adjust as required.
Lubricate.*
Sprockets
Check set screw tightness
Fasteners
Check & tighten as required
Manual Disconnect
Check & Operate
Bearings & Shafts
Check for wear & lubricate
MAINTENANCE SCHEDULE