
WIRING OF CONTROL / SUMMARY
a) start with 230Volts supply cable.
Run cable through large cable bushing on the lefthand side.
b) Attach cable eye to ground wire. Then connect ground wire to
base plate with washer and nut (exactly as shown in picture detail).
Connect all other cables to control.
CABLES AND WIRING
The usage of shielded cable in order to connect the motor to control board is highly recommended. Magnetic and inductive in uence of the signal in
the cables can produce electric noise and may disturb the function of the gate .
Generally avoid:
- Control board location far away from gate.
- 230Volt and low voltage in the same power line. Not allowed by electrical rules.
- Wiring of the infrared sensors, switches, ashing lamps & electric locks require a cable separately from the motor wiring.
- Other wirings like telephone intercoms, lights for garden etc. must be in separate cables.
- Rigid copper cables especially when thicker diameters are dif cult to manage during the installation and may result in bad connections with
functional issues. Use instead exible cables.
- Cable material not suitable for outside use. Use cables suitable for outside use and underground. Run the cables in conduits if the cable is not
suitable for placing in the ground (armoured or suitably protected). You may also consult your local electrician.
We recommend the following accessories:
- LA400-JB40E Kit for cable extension of one installation unit. Consists of 12m of cable 6-pole with identical colours, distribution box IP65,cable
screw joints and fastening material.
- 041ASWG-0482-50 Cable 50m for professional use. Consists of 50m of cable 6-pole with identical colours. Cut only as much as you need for the
current installation.
General wiring sizes:
The numbers mentioned in the table below are minimum requirements. It is always possible to use larger diameters.
- 230Volt Supply Power to controller: min. 0,75mm² 3-pole
- 230Volt Supply transformer installed separately (i.e. in the garage) and low voltage to gate. See table.
- Motor wiring: 2 wires min. 1,0mm², 4 wires min. 0,75mm² (or shielded cable)
- Electric locks: See table
- Switches, infrared sensors, ashing lamp: See table etc. min.0,5mm²
4/16 en
Operator Model
LYN, SCS, ART
motor wiring
SUB (underground)
motor wiring
Transformer separately
installed (in garage) and
low voltage supplied to
control board box.
Electric lock (12Volt)
wiring
External antenna
(Remove original
antenna of logic board)
Switches, Flashing lamp
etc.
Infrared Sensors
Distance
0m - 6m
2 x 1,0mm²
4 x 0,75mm²
2 x 1,0mm²
3 x 0,75mm²
0,75mm²
0,75mm²
Coax cable (Satellite
cable)
50 Ohm
0,5mm²
0,5mm²
Distance
6m - 10m
2 x 1,0mm²
4 x 0,75mm²
2 x 1,0mm²
3 x 0,75mm²
0,75mm²
0,75mm²
Coax cable (Satellite
cable)
50 Ohm
0,5mm²
0,5mm²
Distance
10m - 12m
Normal
Wiring
Use shielded cable for
the 3 smaller motor wires
1,0mm²
1,0mm²
Coax cable (Satellite
cable)
50 Ohm
0,75mm²
0,75mm²
Distance
12m – xx
Max. 15m
Use shielded cable for the 4
smaller motor wires.
Use shielded cable for the 3
smallermotor wires
Max. 30m; Min. 1,5mm²
Gate weight maximum 50% of
maximum motor power rating.
Max. 30m; Min. 1,5mm²
Coax cable (Satellite cable)
50 Ohm
(max. 25m)
Min. 0,75mm²
Max. 30m
Min. 0,75mm²
Max. 20m
Содержание LiftMaster PROFESSIONAL LYN300 Series
Страница 40: ...2 ru 90 115 115 3A F 200 3F 5 5D 5C 1 207917 2 135 230 30 30 24 230 D E F F 2 3 4 5...
Страница 42: ...1 LY N 230V olt LY N SCS SCS SCS LY N 1 2 A B C D E F Series 200...
Страница 43: ...2 1150 900 900 900 1150 900 900 900 1150 1150 B 3 A C D E F...
Страница 45: ...14 cm 14 cm B A min 6x50 5 A B C D 6 4 Opener MUST be level...
Страница 46: ...7 A 7 A 7 A B B LYN Series SCS Series LYN Series SCS Series SCS Series 5...
Страница 47: ...1 Brown 2 Green 3 White 4 Yellow 5 Blue 6 Red CB24 1 L 2 N 3 L 4 CB11 CB1 GOC1A 24Volt 230Volt 8 6...