SpaceKeeper Cons ole (SKC) – Ins tallation Operation Maintenance Manual

4

INSTALLATION

receptacle plate to the floor, through the two mounting slots found on the

lower lip of the plate.

6. Firmly grasp the front panel cover of the cons ole and remove it by lifting it up

and away from the heat pump unit.

7. With the front panel cover removed, locate the three fluid hos es that are

attached to the unit’s s upply, return, and condens ate connections . Carefully

remove thes e hoses . The s upply and return hos es have swivel connectors .

The condens ate hos e has a hos e clamp.

8. Permanently affix the threaded end of the supply and return hos es (NOT the

s wivel connector) to the building’s s upply and return lines which protrude

through the piping-and-receptacle plate. Slide condens ate hos e over

condens ate line and attach with hose clamp s upplied.

9. Pos ition the heat pump unit agains t the wall and over the piping-and-

receptacle plate. Make s ure to center the unit along the center-line marker

which is engraved into the plate.

10. The three hos es that have been affixed to the building’s s upply, return, and

condens ate piping s hould at this point be acces s ible through the bottom of

the heat pump unit. Us ing the s wivel connectors , re-connect the s upply and

return hoses to the appropriate locations on the heat pump unit. Attach

condens ate hos e to drain pan of unit and attach with hos e clamp provided.

11. Next affix the heat pump unit to the back wall through the mounting holes

us ing appropriately s ized s crews . A screwdriver extens ion may be required in

order to work around the fan. For plates with fres h air damper option connect

the two wires with s pade terminals from the unit to the damper terminals .

12. If further support is neces s ary, two additional mounting holes can be

acces s ed by removing the unit’s cabinet cover. In order to unfasten this

cover, two s crews – one located on each s ide of the unit – mus t be removed.

The two additional mounting holes will be located in the top left and right

corners .

13. Connect the room temperature s ens or to the electrical panel as indicated on

the wiring diagram. Plug the unit’s electrical cord into the s upply outlet that

is located behind the unit.

14. Re-attach the heat pump unit’s cabinet cover (if applicable), and front

panel cover. Ins tallation of the unit is now complete.

Содержание SKC-008

Страница 1: ...Installation Operation Maintenance SpaceKeeper Console Hybrid Heat Pump SpaceKeeper Console SKC Models SKC 008 015 REV 02...

Страница 2: ...6 CoolStart Up 7 CoolOperation 7 OperationalAlgorithm 9 ThermostatConnections 10 Shutdown Output 10 Fault AlarmOutput 11 4 COMMISSION START UP 12 5 MAINTENANCE 14 SKC 008 SKC 015 Wiring Diagram 16 6 A...

Страница 3: ...ons of extreme temperature or humidity Subjecting the unit to conditions of this nature may result in significantly reduced performance reliability and operational life The unit is intended for interi...

Страница 4: ...175 Unit Dimensions Model No Unit Dimensions inches L x W x H Water Connections Inlet Outlet inches Filter Dimensions inches L x W x H SKC 015 48 0 x 12 0 x 25 3 FPT 29 5 x 1 0 x 12 0 SKC 012 48 0 x...

Страница 5: ...llation Procedure 1 This heat pump unit is to be installed within an indoor environment Locate the unit in an area where the surrounding air temperature is above 45 F 7 C at all times Do not attempt t...

Страница 6: ...to the building s supply return and condensate piping should at this point be accessible through the bottom of the heat pump unit Using the swivel connectors re connect the supply and return hoses to...

Страница 7: ...ed equipment located within the building mechanical room is configured to automatically provide each heat pump with water at the appropriate temperature Board Description The unit s electronic circuit...

Страница 8: ...rant Temperature Tw Outgoing Water Temperature Co Condensate Level Ta Tr And Tw are 10k Ohm NTP thermistors while Co is a 100 Ohm NTP thermistor These inputs do not have LED indicators Fan 1 A fan cal...

Страница 9: ...me situations particularlywhen the unit is cold the pressure switch will open during start up If the switch does not close within the 5 minute ignore period the compressor will immediatelybe turned of...

Страница 10: ...be set to alarm however if the open switch closes within 10 minutes a restart cycle is initiated The restart cycle begins with a 10 minute delay after which if there is a cool call in place and all o...

Страница 11: ...el rises above the sensor it will not warm up during the heating cycle and the temperature change will be insignificant It is this lack of temperature change that the controller sees as an impending c...

Страница 12: ...le with standard thermostats and require Heat Pump Thermostats These thermostats call for both heating and cooling on one of the signal wires These thermostats are completely incompatible with CGC s c...

Страница 13: ...an be initiated individually with on board 24V power This capability allows unit or compressor shutdown based on a door switch a light switch or occupancyswitch A separate 24V power supply is required...

Страница 14: ...en all isolation valves to the unit With the unit in operation ensure that the entering and leaving fluid temperatures are acceptable There is typically an 8 to 12 degree drop or rise in temperature d...

Страница 15: ...lean Unit Filter Confirm that the unit filter that is being used is clean A clean filter contributes to the proper operation of the unit byensuring that there is adequate air flow across the coil Fan...

Страница 16: ...an Motors Annually All CGC Hybrid Heat Pumps are permanentlylubricated when shipped from the factory Do not oil or lubricate the fan motors Visual Inspection Visually inspect units and give special at...

Страница 17: ...check the unit for a dirty air filter abnormal entering leaving water temperature inadequate water flow or internal malfunctions that may be causing high or low pressure conditions If the unit contin...

Страница 18: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 16 MAINTENANCE STANDARD WIRING DIAGRAM...

Страница 19: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 17 DETAILS SpaceKeeper Console Dimensional Diagram Complete Unit SpaceKeeper Console Dimensional Diagram Chassis...

Страница 20: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 18 DETAILS Dimensional Diagram Piping andReceptacle Plate Note The fresh air damper mechanism is optional...

Страница 21: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 19 DETAILS SpaceKeeper Console Hose Assembly Connection...

Страница 22: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 20 DETAILS SpaceKeeper Console Hose Assembly Connection...

Страница 23: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 21 DETAILS SpaceKeeper Console Hose Assembly Connection...

Страница 24: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 22 DETAILS...

Отзывы: