background image

SpaceKeeper Cons ole (SKC) – Ins tallation Operation Maintenance Manual

9

OPERATION

by the anti-recycle timer. A flash code of 2 will be initiated upon a low

refrigerant temperature s hutdown.

e. If the

outgoing system fluid temperature

ris es above 140

F, compres s or

operation will be dis abled. The compres s or will be enabled as s oon as
the temperature drops below 120

F. The outgoing s ys tem fluid sens or is

mounted on the leaving fluid pipe. Actual compress or res tart will be

delayed a minimum of 5 minutes by the anti-recycle timer. A flas h code

of 3 will be initiated upon a high outgoing sys tem fluid temperature

s hutdown.

f. If the

discharge air temperature

drops below 40

F, compress or operation

will be disabled. The compress or will be enabled as s oon as the
temperature ris es above 55

F. The discharge air temperature s ens or is

mounted on the fan hous ing. Actual compres s or res tart will be delayed

a minimum of 5 minutes by the anti-recycle timer. A flas h code of 4 will

be initiated upon a low dis charge air temperature s hutdown.

g. The condens ate level s ens or is a 100 ohm thermistor that is heated for

15 seconds every 4 minutes ; its temperature is meas ured at the

beginning and end of this heating cycle. If the condens ate level ris es

above the s ens or, it will not warm up during the heating cycle, and the

temperature change will be ins ignificant. It is this lack of temperature

change that the controller s ees as an impending condens ate overflow.

When a high condens ate level is detected, compres s or operation is

immediately terminated, and at the same time the fan is s topped for 30

s econds , and then res tarted. At this time a flas h code of 7 will be

initiated. The 4 minute cycle will continue until the cooling call is no

longer in place. If the condensate level drops below the s ens or,

compres s or operation will be returned to normal. However, if the

condens ate level s tays above the s ens or for more than 15 minutes , the

fault alarm will be triggered. This fault s ignal will automatically be

res et once the condens ate level goes below the s ens or.

Note

: The las t flas h code will be maintained in memory for one week or until the unit

controls are powered down. The flash code will continue until the problem has cleared

and the compres sor has been put into operation. If a cooling call is in place, it mustbe

dis engaged before the caus e of the las t alarm s hutdown can be identified.

Operation Algorithm

There are several control algorithms to prevent cycling and problematic operation.These

are:

1. Double Call – If the thermos tat connection or s et up is incorrect res ulting in a

s imultaneous call for both heating and cooling, the unit will not operate. This

Содержание SKC-008

Страница 1: ...Installation Operation Maintenance SpaceKeeper Console Hybrid Heat Pump SpaceKeeper Console SKC Models SKC 008 015 REV 02...

Страница 2: ...6 CoolStart Up 7 CoolOperation 7 OperationalAlgorithm 9 ThermostatConnections 10 Shutdown Output 10 Fault AlarmOutput 11 4 COMMISSION START UP 12 5 MAINTENANCE 14 SKC 008 SKC 015 Wiring Diagram 16 6 A...

Страница 3: ...ons of extreme temperature or humidity Subjecting the unit to conditions of this nature may result in significantly reduced performance reliability and operational life The unit is intended for interi...

Страница 4: ...175 Unit Dimensions Model No Unit Dimensions inches L x W x H Water Connections Inlet Outlet inches Filter Dimensions inches L x W x H SKC 015 48 0 x 12 0 x 25 3 FPT 29 5 x 1 0 x 12 0 SKC 012 48 0 x...

Страница 5: ...llation Procedure 1 This heat pump unit is to be installed within an indoor environment Locate the unit in an area where the surrounding air temperature is above 45 F 7 C at all times Do not attempt t...

Страница 6: ...to the building s supply return and condensate piping should at this point be accessible through the bottom of the heat pump unit Using the swivel connectors re connect the supply and return hoses to...

Страница 7: ...ed equipment located within the building mechanical room is configured to automatically provide each heat pump with water at the appropriate temperature Board Description The unit s electronic circuit...

Страница 8: ...rant Temperature Tw Outgoing Water Temperature Co Condensate Level Ta Tr And Tw are 10k Ohm NTP thermistors while Co is a 100 Ohm NTP thermistor These inputs do not have LED indicators Fan 1 A fan cal...

Страница 9: ...me situations particularlywhen the unit is cold the pressure switch will open during start up If the switch does not close within the 5 minute ignore period the compressor will immediatelybe turned of...

Страница 10: ...be set to alarm however if the open switch closes within 10 minutes a restart cycle is initiated The restart cycle begins with a 10 minute delay after which if there is a cool call in place and all o...

Страница 11: ...el rises above the sensor it will not warm up during the heating cycle and the temperature change will be insignificant It is this lack of temperature change that the controller sees as an impending c...

Страница 12: ...le with standard thermostats and require Heat Pump Thermostats These thermostats call for both heating and cooling on one of the signal wires These thermostats are completely incompatible with CGC s c...

Страница 13: ...an be initiated individually with on board 24V power This capability allows unit or compressor shutdown based on a door switch a light switch or occupancyswitch A separate 24V power supply is required...

Страница 14: ...en all isolation valves to the unit With the unit in operation ensure that the entering and leaving fluid temperatures are acceptable There is typically an 8 to 12 degree drop or rise in temperature d...

Страница 15: ...lean Unit Filter Confirm that the unit filter that is being used is clean A clean filter contributes to the proper operation of the unit byensuring that there is adequate air flow across the coil Fan...

Страница 16: ...an Motors Annually All CGC Hybrid Heat Pumps are permanentlylubricated when shipped from the factory Do not oil or lubricate the fan motors Visual Inspection Visually inspect units and give special at...

Страница 17: ...check the unit for a dirty air filter abnormal entering leaving water temperature inadequate water flow or internal malfunctions that may be causing high or low pressure conditions If the unit contin...

Страница 18: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 16 MAINTENANCE STANDARD WIRING DIAGRAM...

Страница 19: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 17 DETAILS SpaceKeeper Console Dimensional Diagram Complete Unit SpaceKeeper Console Dimensional Diagram Chassis...

Страница 20: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 18 DETAILS Dimensional Diagram Piping andReceptacle Plate Note The fresh air damper mechanism is optional...

Страница 21: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 19 DETAILS SpaceKeeper Console Hose Assembly Connection...

Страница 22: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 20 DETAILS SpaceKeeper Console Hose Assembly Connection...

Страница 23: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 21 DETAILS SpaceKeeper Console Hose Assembly Connection...

Страница 24: ...SpaceKeeper Console SKC Installation Operation Maintenance Manual 22 DETAILS...

Отзывы: