CET s.r.l.                                                                                                                                                                   Parallel Message Display 

 

 

page 8

 

The  display  unit  reads  the  9  inputs  as  direct  contacts  and  the  closure  of  each  of  them  causes  the  associated 

message to be displayed, The message disappears when the input reopens. 

In case of several inputs closing at the same time, the display unit shows the message associated to the lower 

input from D0 to D8, with priority to D0. 

 

 

2.3.4.  Command TYPE 8: Continuous message recall in BINARY code 

 

 

Inputs 

SY 

Command TYPE 8 

 

 

This command enables the display unit to use the first 9 inputs in a DIRECT mode with BINARY coding: 

 

D8 

D7 

D6 

D5 

D4 

D3 

D2 

D1 

D0 

 

 

 

 

 

 

 

 

 

2

8

 

2

7

 

2

6

 

2

5

 

2

4

 

2

3

 

2

2

 

2

1

 

2

0

 

 

Number in the range 0 to 512 

 

The message associated to the current number is continuously displayed as long as such number is sent to the 

input. With this configuration, you cannot use any of the commands of TYPES  0 to 7. 

 

2.3.5.  Command TYPE 11: Sub-message display in BINARY code 

 

 

Using  this  command,  you  can  recall  a  message  to  the  second  display  line  together  with  the  message  that  is 

already displayed at the moment. 

This enables two different messages being displayed at the same time. Should one or both messages be longer 

than 20 characters, the text will automatically scroll from right to left. 

To remove the message from the second line, send back the same command recalling message no. 0.  

N.B.

 This command is not implemented in the displays with two 40-character lines. 

 

Inputs 

SY 

Command TYPE 11 

IMP 

 

This coding requires entering the message recall number in BCD code: 

 

D8 

D7 

D6 

D5 

D4 

D3 

D2 

D1 

D0 

 

 

 

 

 

 

 

 

 

2

8

 

2

7

 

2

6

 

2

5

 

2

4

 

2

3

 

2

2

 

2

1

 

2

0

 

 

Number in the range 0 to 512 

 

 

 

Coding and number are always read at the variation  0   1 of the synchronism signal SY. 

Содержание Message Dispay AMF401

Страница 1: ...ERIES AMF401 AMF402 BMF202 EMC202 EMC402 EMF202 EMF402 FMC202 Version 1 2 s r l Strada Statale 211 Km 53 550 28071 Borgolavezzaro NO Tel 39 0321 885180 885301 885807 Fax 39 0321 885560 http www cet italy it e mail info cet italy it ...

Страница 2: ...nd TYPE 7 Manual operation and associated commands 11 2 5 2 Command TYPE 10 Message Print 12 2 5 3 Command TYPE 12 Display flashing mode 12 2 5 4 Command TYPE 14 System language selection Message bank selection 12 3 TECHNICAL DESCRIPTION 14 3 1 INPUTS 14 3 1 1 Using inputs in POSITIVE logic 14 3 1 2 Using inputs in NEGATIVE logic 15 3 1 3 Input command timing 15 3 2 SERIAL LINE 16 3 2 1 Serial lin...

Страница 3: ...tting at work operations with directs display of internal data variables if any information concerning maintenance operations troubleshooting sequence sequence information in different languages 1 1 GENERAL DESCRIPTION OF THE DIFFERENT MODELS This manual refers to the following models FMC202 EMC202 EMC402 EMF202 EMF402 AMF401 AMF402 BMF202 The message display units mentioned above differ only as r...

Страница 4: ...h high brilliance 1 1 7 AMF 402 SERIES A container front 72 x 288 fluorescent display with 2 lines each of 40 characters 80 characters in all 5 mm character height with high brilliance 1 1 8 BMF 202 SERIES B container front 96 x 288 fluorescent display with 2 lines each of 20 characters 40 characters in all 11 mm character height with high brilliance 1 2 MAIN FEATURES VISUALISATION ON A ALPHANUMER...

Страница 5: ...d contrast MESSAGE NUMBER CAPACITY All devices have a maximum capacity of 512 messages NUMBER OF VARIABLES THAT CAN BE ENTERED with external commands as many characters as the display length INPUTS PRI input for POSITIVE LOGIC or NEGATIVE LOGIC programming 14 DATA inputs for different functions see chart INPUT SIGNAL LEVEL Positive logic 0 0 Vdc to 6 Vdc 1 10 5 Vdc to 30 Vdc Negative logic 0 OFF f...

Страница 6: ...o the display and replaces the previous one or it is possible to manage the 9 data inputs D0 to D8 as independent inputs for contacts by sending the appropriate sequence commands through the PLC it is possible to manage and update directly all or part of determined text areas in the message being displayed by entering the characters required ASCII or BCD In this way you can complete the texts with...

Страница 7: ...ands TYPE 8 1 0 1 1 1 Direct Binary message recall TYPE 9 IMP 1 0 0 0 Not active TYPE 10 IMP 1 0 0 1 Displayed message print enabling TYPE 11 IMP 1 0 1 0 Binary sub message recall TYPE 12 IMP 1 1 0 0 Message flashing mode enabling TYPE 13 IMP 1 0 1 1 BCD sub message recall TYPE 14 IMP 1 1 0 1 System language change Bank selection Each command is stored upon the variation from 0 to 1 of SY excludin...

Страница 8: ... D0 2 8 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0 3 rd 2 nd 1 st 3 rd DIGIT 2 nd DIGIT 1 st DIGIT Number in the range 0 to 199 Coding and number are always read at the variation 0 1 of synchronism signal SY in case of recall using a command type 1 BCD up to 199 messages can be recalled 2 3 3 Command TYPE 6 Message recall through independent inputs Inputs SY D C B A Command TYPE 6 IMP 0 1 1 0 This coding req...

Страница 9: ... as such number is sent to the input With this configuration you cannot use any of the commands of TYPES 0 to 7 2 3 5 Command TYPE 11 Sub message display in BINARY code Using this command you can recall a message to the second display line together with the message that is already displayed at the moment This enables two different messages being displayed at the same time Should one or both messag...

Страница 10: ...a word sentence or number such writings are called VARIABLES as they are continuously varied updated Management and consequently entering of such VARIABLES in the message display unit is rather sophisticated in order to guarantee the PLC easy and efficient display control First of all it is necessary to identify in advance the positions in the text where the variables are to be entered and leave t...

Страница 11: ...GIT 2 nd DIGIT 1 st DIGIT Number in the range 0 to 199 2 4 2 Command TYPE 4 Address in BINARY code Inputs SY D C B A Command TYPE 4 IMP 0 1 0 0 This code informs the display unit that the first 8 inputs represent the position address 0 to 80 in BINARY code where the next variable will be laid D8 D7 D6 D5 D4 D3 D2 D1 D0 2 6 2 5 2 4 2 3 2 2 2 1 2 0 Number in BINARY code in the range 0 to 80 Coding a...

Страница 12: ...osition to lay the variable In this case the actual cursor stays in its initial position and increases by 1 relative to that position 2 4 4 Command TYPE 5 Variable in ASCII code Inputs SY D C B A Command TYPE 5 IMP 0 1 0 1 This coding identifies the presence of a variable ASCII coded character in the first 9 inputs D8 D7 D6 D5 D4 D3 D2 D1 D0 2 8 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0 ASCII character in t...

Страница 13: ...message being displayed through the serial line Inputs SY D C B A Command TYPE 10 IMP 1 0 0 1 Coding and number are always read at the 0 1 variation of the synchronism signal SY 2 5 3 Command TYPE 12 Display flashing mode Using this command you can cause the message shown on the display to flash This is a Set Reset type command i e the first time the input is activated the flashing mode is also ac...

Страница 14: ... you are to work with The bank number is created during programming using the WINTEXT software package Desks can be selected as follows D0 BANK 1 D1 BANK 2 D2 BANK 3 D3 BANK 4 The next 5 bits D4 to D8 select the system message language you are to work with in the following order D4 ITA ITALIAN D5 GB ENGLISH D6 DE GERMAN D7 SPA SPANISH D8 FRA FRENCH Upon power up if no bits are set the instrument r...

Страница 15: ...ITIVE LOGIC by programming the PRI input to EARTH or NEGATIVE LOGIC with PRI at 24Vdc The inputs must be connected as shown in the figure according to the type of logic used POSITIVE or NEGATIVE 3 1 1 Using inputs in POSITIVE logic PRI 24 GND PRI 24 GND 9 A B D0 Dn C PNP E GND EARTH EXTERNAL POWER UNIT GND 24Vdc C Collector E Emitter DISPLAY UNIT C PNP E C PNP E C PNP E ...

Страница 16: ...0 to 1 of the synchronism signal SY should respect the following minimum time conditions For fast VARIABLE updating from the PLC we recommend using the following sequence type T1 T3 T2 T1 T3 T1 minimum 1 millisecond T2 minimum 3 milliseconds T3 minimum 3 milliseconds CODED INPUTS SY 9 A B D0 Dn C NPN E GND EARTH C Collector E Emitter DISPLAY UNIT LOGIC UNIT C NPN E C NPN E C NPN E FIRST VARIABLE S...

Страница 17: ...essages displayed The message display units can also be totally managed controlled through serial line commands instead of parallel inputs 3 2 1 Serial line commands The serial line command generator device PC or PLC LOGIC UNIT should make a 2 byte string of data using the chart of commands for commands TYPE 0 1 2 3 4 5 6 10 11 12 13 and 14 Composition of 1 st string byte START BIT 2 STOP BITS BIT...

Страница 18: ...i e have the same grounding reference for the display unit this is the external power unit since potential differences damage the serial ports 4 2 PROGRAMMED MEMORY ARCHIVES All text programmes resident in the display units can be resent to a personal computer fitted with the WINTEXT software to be filed or changed To execute programme transfer the serial lines of the personal computer and message...

Страница 19: ... 5 1 1 Technical features POWER SUPPLY 24 110 220 Vac 10 15 FREQUENCY 50 60 Hz ABSORPTION 6VA OPERATING TEMPERATURE 0 C 50 C AMBIENT CONDITIONS R H 95 at 40 C without condensate RELIABILITY MCBF 500 000 lines INK RIBBON cartridge type RIBBON CAPACITY 200 000 characters PAPER FEATURES width 69 5 0 5 mm thickness 0 07mm max roll diameter 50 mm PAPER FORWARD SPEED 0 4 lines sec WRITING SPEED 0 4 line...

Страница 20: ...e written paper roll 2 bring paper from the new roll to the printing mechanism opening 3 press the paper feed button until paper comes out of the printing mechanism 4 insert the new roll in its compartment and close the panel The printer ST40 prints on standard paper easy to find on the market Paper specifications are listed in the chapter TECHNICAL FEATURES It is also possible to order paper from...

Страница 21: ...ions and terminals for EMC202 EMC402 EMF202 EMF402 BMF202 PRI POSITIVE GND LOGIC 7 8 1 2 3 4 5 6 7 8 A B C D S D D D Y 0 1 2 1 2 3 4 5 6 7 8 9 D D D D D D P 24 VDC 3 4 5 6 7 8 R GND I CN3 CN2 CN1 PRI NEGATIVE 24 LOGIC 7 9 PRI POSITIVE GND LOGIC 7 8 PRI NEGATIVE 24 LOGIC 7 9 D D D S D C B A 2 1 0 Y 8 7 6 5 4 3 2 1 24 VDC P D D D D D D GND R 8 7 6 5 4 3 I 9 8 7 6 5 4 3 2 1 CN1 CN2 CN3 ...

Страница 22: ... 6 2 1 Overall dimensions for FMC202 6 2 2 Overall dimensions for EMC202 EMC402 EMF202 EMF402 139 45 10 MAX 43 65 15 9 89 144 48 PROBE ALARM BLOCK 15 MESSAGE DISPLAY 188 69 10 MAX 67 56 15 7 78 192 72 PRESSURE SWITCH NO 21 ALARM TURN OFF LOWER BOILER MESSAGE DISPLAY ...

Страница 23: ... 22 6 2 3 Overall dimensions for AMF401 AMF402 6 2 4 Overall dimensions for BMF202 282 69 10 MAX 67 65 15 10 90 288 72 ALARM AT SECTION 18 INSTALLATIONS MESSAGE DISPLAY 282 97 10 MAX 95 50 15 10 75 288 96 PROBE ALARM BLOCK 15 MESSAGE DISPLAY ...

Страница 24: ...CET s r l Parallel Message Display page 23 6 2 5 Overall dimensions for printer ST40 1 144 144 139 139 10 MAX 138 144 20 32 196 Removable terminal board Fixation squares ...

Отзывы: