8 Operation
This chapter is intended for persons who program their locking media with an Update-Terminal.
8.1 Programming Locking media
Procedure:
1. Hold an authorised V-NET locking media in the reading field of the Update-Terminal
(maximum distance ca 10 mm).
The following signal appears:
1x long blue signal followed by blue flashing signals (= Programming is in progress). After the
programming has been completed successfully, the Update-Terminal flashes 1x short green.
The locking media is now programmed.
Troubleshooting:
Signalling
Reason
Solution
You have held a LINE locking media in the
reading field.
Only V-NET locking media can be used
with Update-Terminals.
The locking media has been blocked or is
not valid any more.
Locked or invalid locking media cannot be
used. Contact your system administrator.
It is not possible to write to the locking
media.
a) There is no connection between the
Update-Terminal and the Access-Point.
b) The locking media is defective.
Contact your system administrator.
The locking media was not held close
enough to the reading field of the
Update-Terminal.
Hold the locking media closer to the
reading field of the Update-Terminal.
The reading field of the Update-Terminal
is covered by metallic materials.
Remove the metallic materials from the
reading field of the Update-Terminal.
Page
36
of
41
Update-Terminal
8 Operation