Century S244 Installation and Operation Manual
40
8.4.2 Why the chimney should penetrate the highest heated space
When it is cold outside, the warm air in the house is buoyant so it tends to rise. This
tendency of warm air to rise creates a slight pressure difference in the house. Called ‘stack
effect’, it produces a slightly negative pressure low in the house (relative to outside) and a
slightly positive pressure zone high in the house. If there is no fire burning in a heater
connected to a chimney that is shorter than the warm space inside the house, the slight
negative pressure low in the house will compete against the desired upward flow in the
chimney.
There are two reasons why the
chimney in the house at right will
cold backdraft when it is cold
outside and there is no fire
burning in the stove. First, the
chimney runs up the outside of
the house, so the air in it is colder
and denser than the warm air in
the house. And second, the
chimney is shorter than the
heated space of the house,
meaning the negative pressure
low in the house will pull outside
air down the chimney, through the
stove and into the room. Even the
finest stove will not work well
when connected to this chimney.
8.5 Supply of Combustion Air
In Canada, wood stoves are not required to have a supply of combustion air from outdoors
(except in mobile homes) because research has shown that these supplies do not give
protection against house depressurization and may fail to supply combustion air during
windy weather. However, to protect against the risk of smoke spillage due to house
depressurization, a carbon monoxide (CO) detector/alarm is required in the room in
which the stove is installed. The CO detector will provide warning if for any reason the
wood stove fails to function correctly.
Содержание S244
Страница 9: ...Century S244 Installation and Operation Manual 9 ...
Страница 32: ...Century S244 Installation and Operation Manual 32 Clearances to combustible materials and floor protection ...
Страница 35: ...Century S244 Installation and Operation Manual 35 Clearances for shield construction ...
Страница 48: ...Century S244 Installation and Operation Manual 48 Appendix 4 Exploded Diagram and Parts List ...