Technical instructions Cm Pelet-set 

 

 

DAY 7 = Sunday (LED diode switches on  

 

Next menu Pr05 is entered by SET button. 
 

 

Pr05: Setting activating times (timer)

 

 
Factory setting:

 

OFF

 (turned off) 

Available setting: ON (turned on) and OFF (turned 
off). 
 
Activating  times  enable  independent  burner 
operation  according  to  set  activating  times  and 
days of a week. 3 ON times and 3 OFF times can 
be  set  in  each  day  of  a  week.  Minimum  length  of 
one activating time is 1 hour, and minimum period 
between off time and next on time is 1 minute. ON 
and OFF times may not overlapped. 
 

 

Sub-programme Pr05: Setting activating time 
 
Factory 

setting: 

DAY1=OFF, 

DAY2=OFF,  

                                    DAY3=OFF...

 (all days off). 

Available setting: ON (turned on) and OFF (turned 
off) for each day separately. 
If  setting  activating  times  is  turned  one  (ON),  you 
may select a day on which we want to activate on 
times.  For  example, if  we  wish  to turn  inactivating 
time for Mondays, we have to change DAY1= OFF 
(by “+” or “-“ buttons) to DAY1=ON and then press 
SET button. 
 

 

Sub-programme  Pr05:  Setting  1

st

  activating 

time 

 
“I  On”    refers  to  the  first  firing  time,  factory  set  to 
06:00,  and  “I  OFF”  means  the  first  burner 
extinction time, factory set to 22:00. 

 

Sub-programme  Pr05:  Setting  2

nd

  activating 

time 
 

Next menu “2 On” refers to the second firing time, 
factory turned off (- - : - -

), and “2 OFF” means the 

second burner extinction time, factory turned off (- 
-  :  -  -).  For  turning  on  the  second  activating  time, 
the first burner shut-time must be shorter at least 1 
minute than the second burner firing time. 
 

 

Sub-programme  Pr05:  Setting  3

rd

    activating 

time 

 
Next menu “3 On” refers to the third ignition time, 
factory turned off (- - : - -

), and “3 OFF” means the 

third burner extinction time, factory turned off (- -:- 
-). For turning on the third activating time, the first 
and  second  burner  shut-times  must  be  shorter  at 
least 1 minute than the third burner firing time. By 
next  pressing  of  SET  button  we  move  to  the  next 
day, DAY2 = OFF. 
 

Содержание EKO-CK 20

Страница 1: ...NERGETSKIH URE AJA 40306 MACINEC GLAVNA 12 HRVATSKA tel 040 372 600 fax 040 372 611 TECHNICAL INSTRUCTIONS USE AND MAINTENANCE Cm Pelet set 14 35 kW For boilers EKO CK P 20 40 EKO CK 20 40 EKO CKB P 2...

Страница 2: ...rst firing 7 2 Extinction procedure 8 Control unit operation 8 1 Firing phase 8 2 Transition phase 8 3 Operation phase 8 4 Extinction phase 8 5 Operation with timer 8 6 Anti frost protection programme...

Страница 3: ...llets when required A built in photo cell serves for flame detection in the burner Special shape of a combustion chamber enables good mixing of air and fuel which gives high efficiency of combustion C...

Страница 4: ...fore filling of the tank it is necessary to open the lid on the tank top and check whether the tank is free from solid objects or any other foreign objects which should not be there Assembly of the pe...

Страница 5: ...urner shut down and the error E1 is displayed at control unit LED diode switched on If lower boiler door are opened while the burner is working micro switch on lower boiler door cuts the el power to t...

Страница 6: ...on Button function Safety thermostat button 0 1 Main switch to turn on turn off power supply to the control unit Start stop button on Off By pressing the button for 3 sec the burner turns on While the...

Страница 7: ...ed in the upper display and current time and current temperature in the boiler are written in the lower display Indication of the current sanitary water temperature If the sanitary water sensor is con...

Страница 8: ...Pr02 to ON and by pressing SET button we enter sub programme Pr02 Sub programme Pr02 Sanitary water set temperature Factory setting 50 C Available setting min 40 C max 80 C If is inbuilt sanitary wat...

Страница 9: ...xample if we wish to turn inactivating time for Mondays we have to change DAY1 OFF by or buttons to DAY1 ON and then press SET button Sub programme Pr05 Setting 1 st activating time I On refers to the...

Страница 10: ...pressing button and room thermostat is obligatory set to minimum control unit will monitor temperature in the boiler and sanitary water tank and when it drops below 5 0 C the burner will turn on and h...

Страница 11: ...rently set programme are displayed in the lower display and after that both displays resume their original settings OFF is displayed in the upper display and current time boiler temperature are displa...

Страница 12: ...in the lower display 15 When the burner reaches set output after approx 8 to 15 minutes depending on set power and after the flame is stabilised flue gases have to be analysed and if necessary to per...

Страница 13: ...t reach temperature Tset within 2 minutes the burner resumes to set output and at temperature Tset the burner the burner starts extinction procedure The burner re ignites when the boiler temperature d...

Страница 14: ...rner operation minimum burner work time is 1 hour and min stand by time between two activating times is 1 minute 8 6 Frost protection programme allowed to use only if the room thermostat is connected...

Страница 15: ...me Err will be displayed in the upper display and E230 will be displayed in the lower display indicating that error could be caused by power supply interruption If the main switch turns off or power s...

Страница 16: ...eeding tube LED diode turns on E4 boiler temperature sensor E5 sanitary water temperature sensor E6 flame disappeared E7 error in memory E8 interruption in fan operation E9 backfilling supply tube wit...

Страница 17: ...Photocell does not detect flame in the burner combustion chamber Due to lack of pellets feeding of too moist pellets or due to dirty photocell E7 error in memory Memory failure Resetting of control u...

Страница 18: ...each consumed pellet tank approx 200 kg If required cleaning frequency can be increased or reduced compared to the recommended one depending on quality of pellets and frequency of the burner turning o...

Страница 19: ...onnectors for electrical connections built in below burner cover which power lines in safety rail to connectors are coming from burner bottom see schemes in this manuals not the through cover side of...

Страница 20: ...t be responsible for possible incorrect data caused by printing errors or errors during transcription and in any case it reserves the right to modify its products deemed to be required and useful with...

Отзывы: