Centrometal EKO-CK 20 Скачать руководство пользователя страница 16

 

 

Technical instructions Cm Pelet-set 

 

 

16 

 

Solid fuel firing 

9. Errors 

 
Regardless  the  current  operating  regime  of  the  burner,  if  errors  E1,  E2,  E3,  E7,  E8,  E9  and  E230 
occur,  the  control  unit  will  stop  operation  immediately,  while  in  case  of  errors  E4,  E5  and  E6  burner 
goes  to  extinction  phase.  If  control  unit  is  in  firing  phase  and  flame  has  not  occurred  yet,  due  to 
notification on error, supply, fan and heater will be stopped immediately. 
 
In case of error “Err” appears in the upper display and error type appear appears in the lower display 
and if it is also necessary to carryout extinction phase (in case of E4, E5 and  E6 errors) “Err” appears 
in the upper di

splay and “OFF” and  error type appear alternately in the lower display. 

Error symbols:   - 

E1

 

– safety pressure switch (LED diode   turns on) 

 

 

 - 

E2

 

– firing safety time expired 

 

 

 - 

E3

 

– excessive temperature on feeding tube (LED diode 

 turns on) 

 

 

 - 

E4

 

– boiler temperature sensor 

 

 

 - 

E5

 

– sanitary water temperature sensor 

 

 

 - 

E6

 

– flame disappeared 

 

 

 - 

E7

 

– error in memory 

 

 

 - 

E8

 

– interruption in fan operation 

 

 

 - 

E9

 

– backfilling supply tube with pellets 

 

 

 - 

E230

 

– signal of error E2 or E6 due to power supply interruption  

 

To  enable  control  unit  to  resume  to  normal 
operation,  error  must  be  corrected  and  cancel  it  on 
the  control  unit.  Error  is  cancelled  by  simultaneous 
pressing 

WINTER

  and 

SUMMER 

buttons  and  ''

+

'' 

button.  If  the  error  cause  is  not  repaired,  error 
cannot be cancelled. 

 
9.1. Errors and possible causes 

ERROR 

CAUSE 

WHAT TO DO

 

E1

 

– safety 

pressure switch 

Too high resistance in 
combustion chamber 

Check: 
How much is filled the boiler combustion chamber 
with ash, registers, flue gas tube and chimney; 
whether the pipe between pressure switch and boiler 
door is pressed. , 

E2

 

– firing safety 

time expired

 

Flame does not occur 
within safety time (12 
min.) 

Check whether: 
there are pellets in pellet tank; 
there are pellets in pellet screw feeder; 
pellet feeder flexible tube has slope toward the 

Содержание EKO-CK 20

Страница 1: ...NERGETSKIH URE AJA 40306 MACINEC GLAVNA 12 HRVATSKA tel 040 372 600 fax 040 372 611 TECHNICAL INSTRUCTIONS USE AND MAINTENANCE Cm Pelet set 14 35 kW For boilers EKO CK P 20 40 EKO CK 20 40 EKO CKB P 2...

Страница 2: ...rst firing 7 2 Extinction procedure 8 Control unit operation 8 1 Firing phase 8 2 Transition phase 8 3 Operation phase 8 4 Extinction phase 8 5 Operation with timer 8 6 Anti frost protection programme...

Страница 3: ...llets when required A built in photo cell serves for flame detection in the burner Special shape of a combustion chamber enables good mixing of air and fuel which gives high efficiency of combustion C...

Страница 4: ...fore filling of the tank it is necessary to open the lid on the tank top and check whether the tank is free from solid objects or any other foreign objects which should not be there Assembly of the pe...

Страница 5: ...urner shut down and the error E1 is displayed at control unit LED diode switched on If lower boiler door are opened while the burner is working micro switch on lower boiler door cuts the el power to t...

Страница 6: ...on Button function Safety thermostat button 0 1 Main switch to turn on turn off power supply to the control unit Start stop button on Off By pressing the button for 3 sec the burner turns on While the...

Страница 7: ...ed in the upper display and current time and current temperature in the boiler are written in the lower display Indication of the current sanitary water temperature If the sanitary water sensor is con...

Страница 8: ...Pr02 to ON and by pressing SET button we enter sub programme Pr02 Sub programme Pr02 Sanitary water set temperature Factory setting 50 C Available setting min 40 C max 80 C If is inbuilt sanitary wat...

Страница 9: ...xample if we wish to turn inactivating time for Mondays we have to change DAY1 OFF by or buttons to DAY1 ON and then press SET button Sub programme Pr05 Setting 1 st activating time I On refers to the...

Страница 10: ...pressing button and room thermostat is obligatory set to minimum control unit will monitor temperature in the boiler and sanitary water tank and when it drops below 5 0 C the burner will turn on and h...

Страница 11: ...rently set programme are displayed in the lower display and after that both displays resume their original settings OFF is displayed in the upper display and current time boiler temperature are displa...

Страница 12: ...in the lower display 15 When the burner reaches set output after approx 8 to 15 minutes depending on set power and after the flame is stabilised flue gases have to be analysed and if necessary to per...

Страница 13: ...t reach temperature Tset within 2 minutes the burner resumes to set output and at temperature Tset the burner the burner starts extinction procedure The burner re ignites when the boiler temperature d...

Страница 14: ...rner operation minimum burner work time is 1 hour and min stand by time between two activating times is 1 minute 8 6 Frost protection programme allowed to use only if the room thermostat is connected...

Страница 15: ...me Err will be displayed in the upper display and E230 will be displayed in the lower display indicating that error could be caused by power supply interruption If the main switch turns off or power s...

Страница 16: ...eeding tube LED diode turns on E4 boiler temperature sensor E5 sanitary water temperature sensor E6 flame disappeared E7 error in memory E8 interruption in fan operation E9 backfilling supply tube wit...

Страница 17: ...Photocell does not detect flame in the burner combustion chamber Due to lack of pellets feeding of too moist pellets or due to dirty photocell E7 error in memory Memory failure Resetting of control u...

Страница 18: ...each consumed pellet tank approx 200 kg If required cleaning frequency can be increased or reduced compared to the recommended one depending on quality of pellets and frequency of the burner turning o...

Страница 19: ...onnectors for electrical connections built in below burner cover which power lines in safety rail to connectors are coming from burner bottom see schemes in this manuals not the through cover side of...

Страница 20: ...t be responsible for possible incorrect data caused by printing errors or errors during transcription and in any case it reserves the right to modify its products deemed to be required and useful with...

Отзывы: