Centrometal CentroPelet ZV 20 Скачать руководство пользователя страница 18

GB

RESTART
WATER

System pressure safety

The system pressure is checked electronically and needs 
to be between 0,5 and 2,3 bar. If this is not the case, the 
pellet  boiler  stove  signalises  an  alarm  and  shows  the 
words “

A l a r   P r e s s

” on the display.

Press” on the display. Check the system pressure keeping 
the key 

 pressed for some seconds. You will read the 

bar value on the display.
The  safety  valve  keeps  anyway  the  value  under  2,5  bar 
letting the exceeding water flow out automatically.

Intervention in case of danger

In  case  of  fire,  disconnect  the  power  supply,  use  a  fire 
extinguisher in accordance with, and if necessary, call the 
fire department and then contact an authorised qualified 
technical assistance

Failed light-up

If the flame does not light up during the switching on or if 
the smokes temperature does not reach a suitable value 
in  the  foreseen  time  gap,  the  thermostove  switches  off 
and you will read the words “

A l a r   N o   A c c

” on the display.

Press the key “On/Off” to reset the alarm. Wait until the 
cooling phase is completed, clean the brazier and start a 
new light-up.

Switching off while working

The thermostove suddenly switches off while working (for 
example because it has run out of pellets in the tank or 
because the motor reducer for pellets loading got broken). 
The  thermostove  continues  working  until  the  pellets  left 
in  the  brazier  ends.  You  will  then  read  the  words  “

A l a r

N o   F i r e

” on the display and the stove switches off. Press 

the key “On/Off” to reset the alarm. Wait until the cooling 
phase  is  completed.  Clean  the  brazier  and  start  a  new 
light-up.

These alarms remind you that the brazier must be 
cleaned and installed correctly before switching on 
the thermostove.

There is no power supply

In the event of a power drop longer than one minute, the 
thermostove can exhaust some smoke in the room: this 
causes no risks.
As  soon  as  you  have  the  power  supply  again,  the 
thermostove  will  have  the  words  “

C o o l   F i r e

”  on 

the  display.  After  completing  the  cooling  phase,  the 
thermostove  will  start  up  again  automatically  according 
to the previous settings.

Anomalie dispositivi elettrici

Manual restart thermostat

Do not attempt to start the thermostove 
before the required time or it may get 
blocked. If this occurs, switch off the 

switch on the back of the pellet boiler stove for 1 
minute, set it on again and wait 10 minutes before 
starting the thermostove again.

The power socket where the thermostove 
is connected should be fitted with “earth 
connection complying with regulations in 

force.” The Manufacturer shall not be held respon-
sible for damage to things or people resulting from 
negligent installation.

Содержание CentroPelet ZV 20

Страница 1: ...QUE CentroPelet ZV 20 24 32 TURZV 08 2014 HR Centrometal d o o Glavna 12 40306 Macinec Croatia tel 385 40 372 600 fax 385 40 372 611 TECHNICAL INSTRUCTIONS for installation use and maintenance of pell...

Страница 2: ...Therefore pay attention and use the proper precautions above all in the presence of children elderly or disabled persons and animals Assembly must be performed by authorized persons Authorized Assist...

Страница 3: ...ivil and penal for accidents deriving from the partial or total lack of observance of the instruc tions contained herein We decline every responsibility derived from improper use of the stove from inc...

Страница 4: ...y clothes hangers and suchlike must be kept a suitable distance from the stove Risk of fire Carefully explain that the thermostove is made from ma terial subjected to high temperatures for the elderly...

Страница 5: ...able maintain a minimum distance of 10 cm at the rear A di 40 cm at the side B and 150 cm at the front If the room contains objects which are believed to be particularly delicate such as drapes sofas...

Страница 6: ...less steel pipe must not be used At the bottom of the flue pipe provide an inspection cap to allow periodic checking and cleaning which must be done annually Make a gas tight connection to the flue pi...

Страница 7: ...st be a wind proof type and must be above the ridge Eventual structures or other obstacles that are higher than the chimney cap must not be too close to the chimney cap itself Fig 5 Characteristics of...

Страница 8: ...s a lever to lift the cover Replace the battery observing the correct polarity Fig 4 Size 12V Fig 3 Fig 4 Size 12V Technical Specification Remote Control N B measures with a tolerance of about 10 mm 1...

Страница 9: ...to 1 The LED is on when the parameter UT01 on the menu is not on OFF and the weekly or daily programming are set SET LED SYMBOL DESCRIPTION The LED starts up every time the stove is loading pellets T...

Страница 10: ...To set the water temperature press the key only once You will see the words Set H2o blinking on the upper display You will read the water temperature on the lower display To set the room temperature p...

Страница 11: ...control panel for example 18 C and a sufficient shut down time has elapsed the thermostove will come back on automatically and continue running until again reaching 20 C Regardless of the operation o...

Страница 12: ...ety and can make it back in the system through the inlet pipe causing a phenomenon of oxygen that is highly damaging to life of the boiler To prevent this phenomenon it is possible to apply the follow...

Страница 13: ...en it requires routine and or special maintenance Connect the stove using hoses so that the stove is not too strictly connected to the system and to allow slighht movement The filling pressure of the...

Страница 14: ...ormation of incrustations along the pipes in the boiler and in the heat exchangers Therefore please get your plumber s advice concering Hardness of water circulating in the system to prevent problems...

Страница 15: ...Friday Day 6 Saturday Day 7 Sunday OFF Heating timer thermostat disabled UT07 Week day selection Press button o select the days of the week Press button to enable ON or disable OFF the pellet boiler s...

Страница 16: ...er fuses to protect the electronic boards are to be found on the boards themselves Reduction motor if the motor stops the thermostove continues to function until the flame goes out for lack of fuel an...

Страница 17: ...sensor Check the water sensor is connected Contact an Authorized Assistance Center ALAR ALAR ALAR ALAR ALAR ALAR COOL ALAR ALAR ALAR ALAR SERV Hot temp The smokes temperature exceeds 280 C Smokes sens...

Страница 18: ...he tank or because the motor reducer for pellets loading got broken The thermostove continues working until the pellets left in the brazier ends You will then read the words Alar No Fire on the displa...

Страница 19: ...ould be no residual combustion in the contact zone between the edges of the crucible and the support surface on the door crucible Parts Everyday Every 2 3 days Every week Every 15 days Every 30 days E...

Страница 20: ...tion Check every 60 90 days Cleaning the interior baffle smoke fan compartment Inside the compartment where there is the ash tray there is a second cover fixed by the cockerels which gives access to t...

Страница 21: ...e there is a fuse holding compartment which is located underneath the supply socket With a screwdriver open the cover of the fuse holding compartment and replace the fuse if necessary 3 15 AT delayed...

Страница 22: ...icular Do not touch the thermostove body and the various components do not approach the door it could cause burns Do not touch the exhaust fumes Do not perform any type of cleaning Do not dump the ash...

Страница 23: ...r non original The operations marked in bold type must be carried out by specialised personnel Any kind of tampering or unauthorized substitution of non original of the thermostove can be hazardous to...

Страница 24: ...not closed properly or gaskets worn 5 Boiler temperature is too high 6 Unsuitable pellets 7 Low pellet feed rate 8 Combustion chamber dirty 9 Smoke outlet obstructed 10 Smoke extraction motor failed...

Страница 25: ...fan convention never stops 1 Temperature sensor temperature control defective or broken 2 Fan failure 1 Check operation of the sensor and replace if necessary 2 Check operation of the motor and repla...

Страница 26: ...gh 2 It was set too much power to the implant 1 Lower the temperature in the boiler 2 Reduce the value of operating power The thermostove goes into modulation as it reaches the temperature set on the...

Страница 27: ...GB...

Страница 28: ...2 fax 385 40 372 621 Centrometal d o o shall not be responsible for possible incorrect data caused by printing errors or error made in transcription and all figures and diagrams are for explanatory pu...

Отзывы: