CELLmatic 1502 – GSV/GSF
Issue: 2.1
User Manual
08.02.2004
Page 25 of 51
Thy
-
tronic
I/S – Bjørnevej 8c – DK 7700 Thisted – Tel.: +45 97982344 – Email.: [email protected]
SET POINTS
Set point J
01-01-94 17:25:35
SETPOINT/SETP I-L/SETP. J/
F6 CLA :
F5 NEW (F5) :Min T-oil alarm 10.0 C
F4 NEW (F4) :Min T-oil cut 5.0 C
F3 NEW (F3) :Max T-oil alarm 70.0 C
F2 NEW (F2) :Max T-oil cut 75.0 C
F1 STOP : STOP
F5:
MIN T-OIL ALARM
When the compressor is operating an alarm will be reported if the oil in the oil separator does not reach
this temperature. At the same time the message "ALARM LT-OIL" will appear at the top left-hand
corner of the display.
F4:
MIN T-OIL CUTOUT
The compressor will be stopped if the oil in the oil separator does not reach this temperature, and
"CUTOUT LT-OIL" will appear at the top left-hand corner of the display.
F3:
MAX T-OIL ALARM
If the oil temperature, measured in the oil manifold, is exceeding this temperature an alarm will be
reported, and "ALARM HT-OIL" will appear at the top left-hand corner of the display.
F2:
MAX T-OIL CUTOUT
If the oil in the manifold is exceeding this temperature the compressor will be stopped, and "CUTOUT
HT-OIL" will appear at the top left-hand corner of the display. Alarm and cutout of high oil temperature
has a delay of 3 minutes.