Power Supply Requirements
The Air Handler is a high performance cooling system and with significant power
requirements. Each of the two sections of the unit, evaporator and condenser, requires
its own power source or cord. The amps and watts for the configurations are listed
below.
AH6500 / AH6500S Cord Connected
Evaporator Module
Condenser Module
System
Amps
(FLA)
@ 115V /
60HZ
Breaker
Size
Power
Input
Watts
Amps
(FLA)
@ 115V /
60HZ
Compressor
LRA
Breaker
Size
Power
Input
Watts
Total
Power
Input
Watts
Standard
5.6
15
640
11.46
53.0
25
824
1464
With Humidifier
6.6
15
755
11.46
53.0
25
824
1579
With Heating
10.6
15
1220
11.46
53.0
25
824
1579
AH8500 / AH8500S Cord Connected
Evaporator Module
Condenser Module
System
Amps
(FLA)
@ 115V /
60HZ
Breaker
Size
Power
Input
Watts
Amps
(FLA)
@ 115V /
60HZ
Compressor
LRA
Breaker
Size
Power
Input
Watts
Total
Power
Input
Watts
Standard
5.6
15
640
11.4
54.5
25
958
1598
With Humidifier
6.6
15
755
11.4
54.5
25
958
1713
With Heating
10.6
15
1220
11.4
54.5
25
958
1713
AH6500S Permanently Connected
Evaporator Module
Condenser Module
System
Amps
(MCA)
@ 115V /
60HZ
Breaker
Size
Power
Input
Watts
Amps
(MCA)
@ 115V /
60HZ
Compressor
LRA
Breaker
Size
Power
Input
Watts
Total
Power
Input
Watts
Standard
3.5
15
320
17.1
53.0
25
1144
1464
With Humidifier
4.5
15
435
17.1
53.0
25
1144
1579
With Heating
11.3
15
1220
17.1
53.0
25
1144
1579
AH8500S Permanently Connected
Evaporator Module
Condenser Module
System
Amps
(MCA)
@ 115V /
60HZ
Breaker
Size
Power
Input
Watts
Amps
(MCA)
@ 115V /
60HZ
Compressor
LRA
Breaker
Size
Power
Input
Watts
Total
Power
Input
Watts
Standard
3.5
15
320
16.9
54.5
25
1278
1598
With Humidifier
4.5
15
435
16.9
54.5
25
1278
1713
With Heating
11.3
15
1220
16.9
54.5
25
1278
1713
Notes:
1. Electrical ratings are for evaporator and condenser fans set on high speed.
2. Two dedicated non-GFI power supply circuits are required, one for each module.