background image

 

37

 

 

 

Troubleshooting Issues – Split System Configuration Only 

Issue Possible 

Causes 

Potential 

Solutions 

No cooling: no refrigerant flow. 

If the "snowflake" icon is 
illuminated on the 
temperature display control, 
the optional liquid line 
solenoid should be 
energized and the 
compressor running. 

No power to liquid

solenoid valve coil 

(valve control) 

Power supply to Evaporator interrupted. Restore 
power. 
Power supply to solenoid coil interrupted: loose 
wire. Inspect for loose fan wiring and reconnect. 

Solenoid coil 
failure 
(valve 
control) 

When the Evaporator is powered on and off, a 
distinct "click" should be heard indicating the 
opening/closing of the solenoid valve. If not, the 
solenoid coil may need to be replaced. Consult 
factory. 

No power to 
compressor 

Power supply to Condensing Unit interrupted. 
Restore power. 

Check for loose wires and reconnect. 
Low pressure switch is open: make sure solenoid 
is energized and condensing unit service valves 
are open. Jumper out switch to check for a faulty 
switch, and replace if necessary. Note that in 
installations below 0°F this switch may remain 
open. Valve Option only. Consult factory. 
High pressure switch is open: make sure 
condensing unit service valves are open. If this 
does not correct the problem, refer to the "High 
Pressure Safety Shutdown" section. 

High pressure 
safety shutdown / 
high discharge 
pressure 

Locate and correct source of high condensing 
head pressure: 

Refrigeration line blockage 
Condenser fan not operating in ambient 
temperatures above 90°F. Ensure that there is 
power to the Condensing Unit and verify the fan 
cycling control settings (optional item). Replace 
condenser fan and fan cycling control if 

 

Insufficient ventilation: reference Condensing 
Unit installation guidelines for proper placement 
and ambient temperature requirements. Correct 
to ensure adequate air ventilation to and from the 
Condensing Unit. 
Improper refrigerant charge: inspect for over-
charged system or non-condensibles in system. 

Dirty or obstructed condenser coil: clean and 
remove all obstructions to airflow. 

Intermittent power 
to compressor 

Check for loose wires and secure. 

Compressor cycling on internal thermal overload 
protection. Replace start capacitor/relay 
assembly 

Compressor cycling on high pressure - see "High 
pressure safety shutdown" section. 

Faulty compressor. Consult factory. 

Содержание AH6500

Страница 1: ......

Страница 2: ...al Humidifier If you have any questions about your new cooling unit it is likely that you will find the answers in this Owner s Manual We also have more information on our website including the latest...

Страница 3: ...s I Specifications Cut Sheets and Cellar Construction 4 II Installation Instructions 9 III Operating Instructions 24 IV Troubleshooting 33 V Limited Warranty 39 VI Support and Data Service Sheet Split...

Страница 4: ...No Humdifier With Humidifier Model Dimensions WxDxH inches Weight lbs Dimensions WxDxH inches Weight lbs AH6500 18 6 x 18 6 x 37 8 161 33 0 x 18 6 x 37 8 181 AH8500 18 6 x 18 6 x 37 8 170 33 0 x 18 6...

Страница 5: ...5...

Страница 6: ...6...

Страница 7: ...electrical outlets and or switches pipes vents and light fixtures be sealed to prevent air and moisture from entering the cellar If there is a leak in the cellar the cooling unit will build up excess...

Страница 8: ...the evaporator coils heat is removed from the air and the resulting cold air is exhausted into the cellar On non ducted installations a minimum clearance of 12 is required from all air intake and dis...

Страница 9: ...ovided leveling feet must be removed The condenser can be provided with grills to vent the air or duct adapters to duct the intake discharge or both The condenser module can also pass through the cell...

Страница 10: ...10...

Страница 11: ...air provided that the location is suitably ventilated or with duct adapters for ducting the intake discharge or both to a suitably ventilated area The unit may be floor mounted on the provided levelin...

Страница 12: ...by four 1 4 20 bolts secured to weld nuts located in the bottom corners The module may be ceiling hung using four 1 4 20 threaded rods field provided attaching to captive nuts provided in the top cor...

Страница 13: ...13...

Страница 14: ...en designed to minimize the amount of condensation created when cooling The condensate that does form on the evaporator will gather in a tray and be channeled to the drain through a small trap and the...

Страница 15: ...Power Input Watts Standard 5 6 15 640 11 4 54 5 25 958 1598 With Humidifier 6 6 15 755 11 4 54 5 25 958 1713 With Heating 10 6 15 1220 11 4 54 5 25 958 1713 AH6500S Permanently Connected Evaporator M...

Страница 16: ...figuration Permanently Connected Valve Only Models in the Split Permanently Connected configuration must be field wired to two dedicated 115V 60HZ circuit breakers sized by model and module according...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...ting expansion valve superheat 8 Insulated suction line refrigeration piping in accordance with Line Sizing Chart 9 5 8 ODS suction service valve located on Condenser Module WHEN BRAZING COPPER TUBING...

Страница 20: ...d leak free system 1 The Condensing unit is pre charged with compressor oil To avoid moisture contamination of the oil do not leave the service valves open to atmosphere for more than 15 minutes 2 Ope...

Страница 21: ...ment it may be necessary to block off the condenser air intake to force the condensing temperature higher If the sight glass is not clear slowly add vapor refrigerant though the suction service valve...

Страница 22: ...eep note of them as they will be required for the Service and Support Data Sheet which initiates the warranty Continue charging until system has sufficient refrigerant for proper operation Do not over...

Страница 23: ...ting losses Summary Keep in mind the following guidelines when selecting your wine cooling unit from CellarPro If the cellar is too large for the cooling unit the cooling unit will be unable to mainta...

Страница 24: ...moved and or shipped in the upright position Be careful when turning the unit on its side The unit NEVER should be turned upside down Temperature Control CellarPro cooling units are designed to turn o...

Страница 25: ...ement options 900W and 1800W An application chart is shown below to assist in selecting the correct wattage For the majority of applications the 900W heater is recommended 900W Heater Specifications 1...

Страница 26: ...lowing section 2 Fan Speed Selector Switch Low Med High The fans on both the evaporator and condenser modules operate on 3 speed settings Low Medium and High For optimum sound and energy efficiency se...

Страница 27: ...the control to air temperature If used to measure air temperatures the differential HY on the cooling unit should be set to 4 If used to measure liquid temperature the differential should be set to 1...

Страница 28: ...e 1 P1 located behind the front grill of the cooling unit Power On Off Press Power On Off to turn the unit on and off When the Compressor On indicator light is on the Compressor is running When the Fa...

Страница 29: ...ferential of 4 F This means that the cooling unit will turn on when the display rises above 62 F 58 F 4 F and turn off when the display falls below 58 F In this example the average temperature inside...

Страница 30: ...conds again The Quick Chill indicator light will turn on when the cooling unit is in Quick Chill mode In the Quick Chill mode the cooling unit will run continuously for 6 hours or until the intake tem...

Страница 31: ...loading warm bottles in the cabinet Auto Defrost Mode The cooling unit has a factory default defrost cycle that initiates every 16 hours for 20 minutes When the cooling unit is in auto defrost mode th...

Страница 32: ...etting is 0 6 TEMPERATURE DIFFERENTIAL The factory preset for this setting is 4 This setting determines the Temperature Differential and therefore the temperature at which the cooling unit will cycle...

Страница 33: ...has failed The cooling unit enters a timed auto cycle mode until Probe 1 is repaired or replaced In this mode the cooling unit will turn on for 12 minutes and off for 8 minutes Please call CellarPro a...

Страница 34: ...bstructions to air flow to or from the unit 2 Check to make sure the condenser filter is clean 3 Increase the supply of cool air to the space outside the condenser coils using a fan ducting or an exha...

Страница 35: ...cellar If the alarm happens in conjunction with hot ambient conditions we recommend doing the following 1 Raise the Minimum Set Point to 60 F until temperatures cool down 2 Increase the FON setting I...

Страница 36: ...t factory No cooling Evaporator fan not blowing If the fan icon is illuminated on the temperature display control the fan should be blowing air No power to fan Power supply to Evaporator interrupted R...

Страница 37: ...this switch may remain open Valve Option only Consult factory High pressure switch is open make sure condensing unit service valves are open If this does not correct the problem refer to the High Pre...

Страница 38: ...e of 16 hours by changing second level parameter idF to a minimum setting of 4 hours If this corrects the problem optimize the defrost frequency by setting and observing the system at different set po...

Страница 39: ...stalling the cooling unit from the wine cellar The limited warranty applies only to cooling units purchased from the factory or an authorized dealer Damage caused by others or by any cause beyond the...

Страница 40: ...length ft Condensing Unit Serial Liquid line diameter OD Evaporator Model Suction line diameter OD Evaporator Serial Operational Data Take the following measurements during a normal refrigeration cycl...

Отзывы: