LINE SET PIPING DIAGRAMS
These are two suggested examples
for running the line set from the coil
to the condensing unit. Example 1
is specifically applicable when
the system is installed with the
condensing unit below or leveled to
the coil. Example 2 is applicable
when the system is installed with
the condensing unit at a
higher elevation than the
coil.
Reverse oil
return bend
Oil saving bend
Suction Line
Evaporator
Coil
Within 16' of height
Downward slope
pitched toward
compressor
1
/
2
" / 10'
Maximum height difference
betwen condenser and
evaporator should not
exceed 50'
H.E. Condensing Unit
Suction line
Liquid Line
Oil return bend
Oil saving bend
Evaporator coil
50'
Example 1
Example 2
Liquid Line
H.E. Condensing Unit
Page 39