![Ceiec Electric PMC-630 E Скачать руководство пользователя страница 69](http://html1.mh-extra.com/html/ceiec-electric/pmc-630-e/pmc-630-e_user-manual_2579014069.webp)
69
Ceiec Electric Technology
Register
Property
Description
Format
Note
9100
WO
Arm RO1 Close
UINT16
Writing “0xFF00”
9101
WO
Execute RO1 Close
UINT16
Writing “0xFF00”
9102
WO
Arm RO1 Open
UINT16
Writing “0xFF00”
9103
WO
Execute RO1 Open
UINT16
Writing “0xFF00”
9104
WO
Arm RO2 Close
UINT16
Writing “0xFF00”
9105
WO
Execute RO2 Close
UINT16
Writing “0xFF00”
9106
WO
Arm RO2 Open
UINT16
Writing “0xFF00”
9107
WO
Execute RO2 Open
UINT16
Writing “0xFF00”
9108
WO
Arm RO3 Close
UINT16
Writing “0xFF00”
9109
WO
Execute RO3 Close
UINT16
Writing “0xFF00”
9110
WO
Arm RO3 Open
UINT16
Writing “0xFF00”
9111
WO
Execute RO3 Open
UINT16
Writing “0xFF00”
Table 5-25 RO Control
5.10 Meter Information
Register
Property
Description
Format
Note
9800 -
9819
RO
Meter Model
1
UINT16
9820
RO
Firmware Version
UINT16
e.g. 10000 shows the version is
V1.00.00
9821
RO
Protocol Version
UINT16
e.g. 10 shows the version is V1.0
9822
RO
Firmware Update Date:
Year-2000
UINT16
e.g.100110means January
10,2010
9823
RO
Firmware Update Date:
Month
UINT16
9824
RO
Firmware Update Date:
Day
UINT16
9825-9826
RO
Serial Number:
XX(Year-2000) -
XX(Month) -
XX(Lot Number) -
XXXX(Meter Number)
UINT32
e.g. 1001030100 means that this
meter was the 100
th
meter
manufactured in Lot 3 of January,
2010
9827-9828
Reserved
UINT16
9829
RO
Feature Code
UINT16
B3B2B1B0:
0000:
1xE6DI+3RO
Other: Reserved
B5B4:
00: 5A I4 CT
01: 1A I4 CT
10: Reserved
11: Reserved