67
Ceiec Electric Technology
7602
RW
Number of Cycles
2
40/20/10/5
(Default=5)
7603
RW
Pre-fault Cycles
3
0* to 5
7604
RW
WFR Log 2
Recording Depth
1
0* to 6
7605
RW
# of Samples
2
0= 16
1=32
2=64
3*=128
7606
RW
Number of Cycles
2
40/20/10/5
(Default=5)
7607
RW
Pre-fault Cycles
3
0* to 5
Table 5-22 Waveform Recorder Log
Notes:
1)
The total capacity of
WFR 1
and
WFR 2
is 6, i.e.
WFR Log 1 Recording Depth
+
WFR Log 2
Recording Depth
<= 6
2)
The valid WFR formats (# of samples/cycle x # of cycles) include 16x40, 32x20, 64x10,and
128x5.
3)
WFR Log Size = (
Number of Samples
x
Number of Cycles
x 2 + 10) x
Recording Depth.
The
Log Size is rounded up to the nearest kB.
4)
Modifying the Setup Parameters of WFRx will clear the WFRx Log and reset WFRx Pointer
will be reset to “0”.
5.7 SOE Log
The SOE Pointer points to the register address within the SOE Log where the next event will be stored.
The following formula is used to determine the register address of the most recent SOE event
referenced by the SOE Pointer value:
Register Address = 10000 + Modulo((SOE Pointer-1) / 64) x 8
Register
Property
Description
Format
10000 – 10007
RO
Event 1
See Section 5.11.6
SOE Log Data
Structure
10008 – 10015
RO
Event 2
10016 – 10023
RO
Event 3
10024 – 10031
RO
Event 4
10032 – 10039
RO
Event 5
10040 -10047
RO
Event 6
10048 – 10055
RO
Event 7
10056 – 10063
RO
Event 8
10064 – 10071
RO
Event 9
10072 – 10079
RO
Event 10
10080 – 10087
RO
Event 11
10088 - 10195
RO
Event 12