Ceiec Electric Technology
% of Fundamental Method:
Voltage K
th
Harmonic Distortion =
X100%
U
U
1
k
, where U
1
is the Fundamental Voltage
Current K
th
Harmonic Distortion =
%
100
I
I
1
k
X
, where I
1
is the Fundamental Current
% of RMS Method:
Voltage K
th
Harmonic Distortion=
X100%
U
U
2
K
1
K
k
Current K
th
Harmonic Distortion=
X100%
I
I
2
K
1
K
k
The PMC-630E provides the following Harmonic measurements:
Phase A
Phase B
Phase C
Phase N
Harmonics-Voltage
THD
THD
THD
/
TEHD
TEHD
TEHD
/
TOHD
TOHD
TOHD
/
2
nd
Harmonics
2
nd
Harmonics
2
nd
Harmonics
/
……
/
31
st
Harmonics
31
st
Harmonics
31
st
Harmonics
/
Harmonics-Current
THD
THD
THD
THD
TEHD
TEHD
TEHD
TEHD
TOHD
TOHD
TOHD
TOHD
K-Factor
K-Factor
K-Factor
K-Factor
2
nd
Harmonics
2
nd
Harmonics
2
nd
Harmonics
2
nd
Harmonics
……
31
st
Harmonics
31
st
Harmonics
31
st
Harmonics
31
st
Harmonics
dPFa
dPFb
dPFc
/
K Factor
K Factor
K Factor
/
Table 4-8 Harmonics Measurements
The calculation method of K-Factor is listed below:
)
(
)
(
K
2
h
h
1
h
2
h
h
1
h
max
max
h
h
I
h
I
Factor
I
h
= RMS current at the h
th
harmonic
h
max
= the highest harmonic order number
h
= the harmonic order number