![Ceiec Electric PMC-630 E Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/ceiec-electric/pmc-630-e/pmc-630-e_user-manual_2579014059.webp)
59
Ceiec Electric Technology
6025
RW
DI6 Function
UINT16
6026
RW
DI1 Debounce
UINT16
1 to 1000 (ms)
(Default=20ms)
6027
RW
DI2 Debounce
UINT16
6028
RW
DI3 Debounce
UINT16
6029
RW
DI4 Debounce
UINT16
6030
RW
DI5 Debounce
UINT16
6031
RW
DI6 Debounce
UINT16
6032
RW
DI1 Pulse Weight
UINT16
1* to 1000000
(x0.001)
6034
RW
DI2 Pulse Weight
UINT16
6036
RW
DI3 Pulse Weight
UINT16
6038
RW
DI4 Pulse Weight
UINT16
6040
RW
DI5 Pulse Weight
UINT16
6042
RW
DI6 Pulse Weight
UINT16
6044
RW
RO1 Function
UINT16
0=Relay Output*
Others Reserved
6045
RW
RO2 Function
UINT16
6046
RW
RO3 Function
UINT16
6047-6050
Reserved
6052
RW
Ia Polarity
UINT16
0=Normal*
1=Reverse
6053
RW
Ib Polarity
UINT16
6054
RW
Ic Polarity
UINT16
6055
RW
Harmonic Calculation
UINT16
0=Fundamental
1=RMS*
6056
RW
Enable Energy Pulse
UINT16
0=Disabled*
1=Enabled
6057
RW
Pulse Constant
UINT16
0=1000 imp/kxh*
1=3200 imp/kxh
2=5000 imp/kxh
3=6400 imp/kxh
4=12800 imp/kxh
6058
RW
Peak Demand Log &
Max/Min Log
Self-Read Time
2
UINT16
0*
6059
RW
Transient Enable
UINT16
0=Disabled*
1=Enabled
6060
RW
Transient Limit
3
UINT16
5-500 (x0.01 VLL
nominal
)
(Default=50)
6061
RW
Backlight Time-out
4
UINT16
0 to 60 (minutes)
(Default=3)
* Default
Table 5-13 Basic Setup Parameters
Notes:
1)
For 5A configuration, PT Ratio × CT Ratio must be less than 1,000,000
For 1A configuration, PT Ratio × CT Ratio must be less than 5,000,000