press 

 to increase the value displayed or 

 to decrease it, until the temperature 

displayed is 700°C, flashing

press 

En t e r

the controller prompts the time for the fourth time/setpoint pair (STEP no. 3)

press 

 until the time displayed is 00:00, flashing

press 

En t e r

to end the cycle; the controller will exit the modify cycle procedure.

-----------------------------------------------------------------------------------------

Sect. 5) Running a cycle

Select the cycle to be modified: use the 

Se l e c t

P r o g .

  button and the 

and  

  buttons (see 

Sect. 3). The controller is in STOP mode (see the description of the modes). Press the 

STOP

START

 button. The controller will emit a brief audible signal, the light next to the button will 

turn on and the controller will start controlling the temperature of the kiln using the values 

set in the cycle. In this phase, the  

  button can be pressed to display the following 

values, in sequence:

Operating setpoint

Time elapsed since the “start”

Partial energy consumed, since the last “start”

Total energy consumed (this value can be reset; see the corresponding section)

At the end of the cycle, the controller will go into “END” mode, displaying the message 

“END” on the display (MAIN). To return to STOP mode, press the 

STOP

START

 button.

NOTE

IMPORTANT: 

If attempting to run an empty cycle (not programmed, or with the time in 

the first step set to 00.00), the controller will display an error code, “ER26”. The error is 

reset using the 

En t e r

 button.

The controller returns to display the temperature of the kiln if no button is pressed for a 
few seconds.

Sect. 6) Activating the timer for the delayed running of the cycle

Select the group and the desired cycle, see section 3. 

Press the 

 button: the controller, after having emitted a brief audible signal, will start 

a countdown, with the remaining time (in hours:minutes) shown on the “MAIN” display. At 

______________________________________________________________________________________

8

Содержание MicroProgel TC 32

Страница 1: ...ammarby Fabriksv g 43 S 120 33 STOCKHOLM Tel 46 8 658 50 04 Fax 46 8 669 60 98 G teborg Argongatan 8 S 431 53 M LNDAL Tel 46 31 87 51 30 Fax 46 31 87 97 61 Web www cebex se Mail Info cebex se Manual M...

Страница 2: ...user PERS and 9 pre configured FIX cycles 6 Sect 4 Entering or modifying the selected cycle 6 Sect 5 Running a cycle 8 Sect 6 Activating the timer for the delayed running of the cycle 8 Sect 7 Settin...

Страница 3: ...cycle belongs to the user group customisable The FIX light indicates that the cycle belongs to the group of cycles pre configured by the installer Display STEP of the step in progress If the controll...

Страница 4: ...G and STEP displays indicate the cycle and step in progress The group of lights indicate whether in the current step the temperature is increasing heating stabilising or decreasing cooling The energy...

Страница 5: ...e the last time the counter was reset by the user the kWh light is on In START mode Normally the controller displays the temperature of the kiln in C on the MAIN display and the C light is on Pressing...

Страница 6: ...ep flashing If the cycle is empty that is has not yet been entered the time shown will be 00 00 otherwise the previously set time in hours minutes will be displayed e g 02 25 indicates a time of 2 hou...

Страница 7: ...layed is 01 00 that is 1h flashing press En te r the controller prompts the setpoint for the first time setpoint pair STEP no 1 press to increase the value displayed or to decrease it until the temper...

Страница 8: ...d to display the following values in sequence Operating setpoint Time elapsed since the start Partial energy consumed since the last start Total energy consumed this value can be reset see the corresp...

Страница 9: ...ing for the end of the delay time by pressing the S T O P S T A R T button The time displayed can be increased or decreased using the and buttons WARNING changes made in this way to the start delay ti...

Страница 10: ...er ER31 Hardware fault Contact the installer ER41 ER42 Thermocouple continuity failure not connected or connected incorrectly Check the thermocouple and connections ER43 Cold junction temperature sens...

Отзывы: