Using the HB Delay parameter, the alarm intervention can be delayed (menu System, see paragraph 7.2.2).
HB delay (es: 2.5 sec.)
NO ALARM
22: R (V/I)
HB sense (+20%)
26,4
30
25
20
15
10
5
0
Ohm
HB delay (es: 2.5 sec.)
ALARM
22: R (V/I)
HB sense (+20%)
26,4
30
25
20
15
10
5
0
Ohm
Sensitivity (HB sense) and delay (HB delay) can be varied according to the application (menu System, see
paragraph 7.2.2).
8.2 Short Circuit
This alarm is activated if the unit detects a short circuit in one of the power devices. This alarm could also
activate when the current measured by the unit is greater than 80% of the value set in Nominal I.
8.3 Thermal alarm
When the heatsink temperature reaches the temperature set in the “Temperature Alarm Setpoint” value the
power output are forced to 0% (see paragraph 7.2.6).