10.5
Technical Specifications
General features:
Cover and Socket material:
PolymericV2
Mounting:
DIN bar
Auxiliary voltage:
90:130V
170:265V
230:345V
300:530V
510:690V
Relay output for Heater Break Alarm
(only with HB option):
0.5A a 125VAC
Input features:
Logic input SSR:
4 ÷ 30Vdc 5mA Max (ON
≥
4Vdc OFF
<
1Vdc)
Analogic input
0 ÷ 10Vdc impedance 15 K ohm
Analogic input
4 ÷ 20mA impedance 100 ohm
POT
15 K ohm min.
Digital Input
4 ÷ 30Vdc 5mA Max (ON
≥
4Vdc OFF
<
1Vdc)
Output features(power device):
Nominal current in continuous service:
See order code
Max peak current (10ms)
400A for unit type 030
600A for unit type 035
800A for unit type 040-45
Voltage range:
24÷600V
Repetitive peak reverse voltage:
1200V
Latching current:
250mA
Leakage current:
15mA eff
I²T value tp=10msec:
830 AV/s for unit type 030
1750 AV/s for unit type 035
3110 AV/s for unit type 040-45
Frequency range:
47÷70Hz
Power loss (I=Inom):
38W for unit type 030
44W for unit type 035
50W for unit type 040
57W for unit type 045
Isolation Voltage:
2500Vac
Содержание Revo M 1PH
Страница 2: ...CD Automation srl REVO M User s Manual REVO_M08 2 ...
Страница 19: ...CD Automation srl REVO M User s Manual REVO_M08 19 11 2 Schematic ...
Страница 24: ...CD Automation srl REVO M User s Manual REVO_M08 24 12 1 Scroll the parameters ...
Страница 32: ...CD Automation srl REVO M User s Manual REVO_M08 32 17 Electronic boards 17 1 How to access ...
Страница 48: ...CD Automation srl REVO M User s Manual REVO_M08 48 ...