7
Basic Connections and sizing
Single phase wiring with resistive load (with REVO M-1PH)
V
P
I
=
V = Nominal voltage of the load
I = Nominal current of the load
P = Nominal power of the load
V
I
Single phase wiring with inductive load (with REVO M-1PH)
φ
cos
V
P
I
=
V = Nominal voltage phase to phase
I = Nominal current to the load
P = Nominal power to the load
Star wiring with resistive load (control on two phases with REVO M-2PH)
V
P
I
73
1
,
=
V = Nominal voltage of the load
I = Nominal current of the load
P = Nominal power of the load
V
I
Delta wiring with resistive load (control on two phases with REVO M-2PH)
V
P
I
73
1
,
=
V = Nominal voltage of the load
I = Nominal current of the load
P = Nominal power of the load
V
I
Star wiring with resistive load (control on three phases with REVO M-3PH)
V
P
I
73
1
,
=
V = Nominal voltage of the load
I = Nominal current of the load
P = Nominal power of the load
V
I
Delta wiring with resistive load (control on three phases with REVO M-3PH)
V
P
I
73
1
,
=
V = Nominal voltage of the load
I = Nominal current of the load
P = Nominal power of the load
V
I
Open Delta wiring with resistive load (with 3 X REVO M-1PH)
V
P
I
3
=
V = Nominal voltage of the load
I = Nominal current of the load
P = Nominal power of the load
V
I
Содержание Revo M 1PH
Страница 2: ...CD Automation srl REVO M User s Manual REVO_M08 2 ...
Страница 19: ...CD Automation srl REVO M User s Manual REVO_M08 19 11 2 Schematic ...
Страница 24: ...CD Automation srl REVO M User s Manual REVO_M08 24 12 1 Scroll the parameters ...
Страница 32: ...CD Automation srl REVO M User s Manual REVO_M08 32 17 Electronic boards 17 1 How to access ...
Страница 48: ...CD Automation srl REVO M User s Manual REVO_M08 48 ...